background image

14

Filter removal through the bottom

10 - Maintenance

10.1 - Air filter

Filters should be frequently cleaned to avoid clogging. They 
should  be  inspected  every  3  or  4  months  under  normal 
operating conditions and be replaced if necessary.

Unit should never be run without filter.

The  filters  can  be  removed  for  cleaning  or  replacement, 
through  the  bottom  or  the  side  of  the  unit  (see  drawings 
below).

Note :

 In case the filters are to be removed from the bottom, 

take off the clips on the filters in order to be able to remove 
them from the casing.

Caution

Before  performing  any  maintenance  operation, 
disconnect the unit main power supply.

10.2 - Condensate drain pan

The condensate pan must be checked periodically to make 
sure that drain piping is not obstructed.
If required, it must be cleaned and rinsed.
The  fan  motor  assembly  bottom  panel  allows  for  easy 
access, if there is no heating coil located downstream the 
cooling coil, to condensate drain pan for cleaning.

10.3 - Coils

Check that coil fins are not clogged or damaged. 
To avoid mouldiness of coils caused by an accumulation of 
fine  dusts,  it  is  recommended  to  clean  them  frequently.  If 
necessary, comb the coil fins with an appropriate tool.

Care must be taken not to damage the fins while cleaning 
them.
The  coils  can  be  removed  for  cleaning  as  shown  on  the 
drawing below.

10.4 - Fan motor assembly

There is no particular maintenance on fan motor assembly. 
The  units  are  equipped  with  permanently  lubricated  fan 
motor  bearings.  It  is  not  necessary  to  add  oil.  However, 
during periodic maintenance, check that fan wheel rotates 
freely without any friction.
If the fan motor overload protection is tripped, wait for safety 
automatic  reset  and  try  to  find  out  the  cause  of  overload 
protection tripping.
Follow the instructions below to remove the motor and fans 
for replacement :

Step 1 : Access panels removal

Disconnect the unit power supply. According to the access 
condition,  remove  either  the  service  side  panel  and  the 
opposite panel or the service side panel and the fan motor 
assembly access panel.

Step 2 : Motor removal

Take  away  the  drive  belt,  then  the  fixing  screws  from  the 
motor platform. Push this platform upward to take it from 
the fans support rails.

It is recommended to proceed to the following maintenance 
works in order to ensure a good operation of the unit.

Filter removal through the side

Coils removal

Clips

Содержание 4.05

Страница 1: ... installation et de maintenance WESPAK 4 05 5 05 6 05 Belt drive compact air handling units Centrales compactes de traitement d air à entraînement par courroies IOM WPKBD N 2GBF 09 08 Part number Code Q3NSTE864 Supersedes Annule et remplace IOM WPKBD N1GBF 06 05 ...

Страница 2: ...II ...

Страница 3: ...arrying out wiring according to the supplied wiring diagram Warning All field wiring must be installed in accordance with the national wiring regulations Warning Installation operation and maintenance must be performed by qualified personnels who are familiar with local codes and regulations and experienced with this type of equipment Warning Confirm the unit is switched OFF before installing or s...

Страница 4: ...05 6 05 Air flow range m3 h 4000 6000 5500 7500 7000 9000 Nominal air flow m3 h 5000 6500 8000 Fan static pressure Pa 400 400 400 Nominal cooling capacity tot sens 1 kW 25 9 19 6 36 0 26 5 43 2 32 0 Chilled water flow l h 4441 6172 7409 Nominal heating capacity 2 kW 21 3 29 9 35 8 Hot water flow l h 1223 1716 2056 FAN Type Double wheel centrifugal Model DA 9 9 N2T DA 9 9 N2T DA 10 10 N2T Drive Adj...

Страница 5: ...17 Number of rows 2 2 2 Number of circuits 15 15 17 Number of empty tubes 0 0 0 Header diameter inlet outlet mm 33 42 33 42 33 42 33 42 33 42 33 42 Water content litres 5 2 6 2 6 8 ELECTRIC HEATER Heating element type à ailettes lisse lisse BE1 capacity kW 12 24 36 BE2 capacity kW 24 36 48 1 BE3 capacity kW 36 1 48 1 60 1 Supply voltage 400 V 3 Ph 50 Hz Neutral Earth AIR FILTERS Filter efficiency ...

Страница 6: ...10 1940 5 Dimensions 5 1 Fixation dimensions a By threaded rods only b By threaded rods and hanger rails Dimensions mm Sizes A B C D E F G H G2 filter G4 filter 4 05 1498 750 1074 1150 633 1690 82 122 485 5 05 1940 750 1274 1350 833 2132 82 122 485 6 05 1940 852 1274 1350 833 2132 82 122 540 1 2 way mixing box 2 Standard casing 3 Silencer casing 4 Electric heater casing ...

Страница 7: ...24 1872 420 62 102 2088 1940 6 05 1880 479 1872 475 62 102 2088 1940 Dimensions mm Sizes H I J K L M N G2 filter G4 filter 4 05 485 1110 1252 1292 1150 1548 950 500 5 05 485 1310 1452 1492 1350 1990 1290 600 6 05 540 1310 1452 1492 1350 1990 1290 600 Side view Rear view Front view Top view Bottom view Remark The dimensions of mixing box connection are identical to those of inlet duct collar connec...

Страница 8: ... 351 50 356 62 485 84 140 226 206 6 05 402 54 407 66 540 84 140 226 206 Installation with 4 row cooling and 2 row heating coils Sizes A B C D E F G H I J 4 05 356 66 339 90 485 63 112 146 178 56 5 05 356 66 339 90 485 63 112 146 178 56 6 05 407 67 390 90 540 66 112 146 178 60 Installation with 6 row cooling and 2 row heating coils Sizes A B C D E F G H I J 4 05 356 66 352 83 485 63 112 168 178 50 ...

Страница 9: ...let and outlet sides of the unit 4 Install the unit in a position from where condensate can be run to waste easily 5 Check the distance between the upper slab and false ceiling to ensure the unit will suit the distance 6 Ensure there is sufficient space around the unit to service it see table hereafter for minimum clearances on service side of filters and fan motor assembly access Warning Do not i...

Страница 10: ...actory fitted assembling clamps and screws 5 Secure the unit in its final position and level it with a spirit level to assure proper drainage and operation 6 Unit must be mounted in such a way that water will flow toward drain connection 6 Installation continued Assembly of two casings Suspension kit hanger rail Factory fitted assembling clamps and screws Final assembly Suspension kit by threaded ...

Страница 11: ... header 7 2 Water coil connections Each water coil is equipped with headers having Ø33 42 male threaded type connection on water supply and water return Air vent must be installed at highest point of the water piping To ensure an optimum heat transfer efficiency connections of water supply and return should be arranged in such a way that a counter flow configuration between air and water is obtain...

Страница 12: ...t in the condensate reception zone example negative pressure 40 mm height A 80 mm height B 160 mm 7 Water Connections continued 7 4 Winterizing water coils In winter due to a general shutdown of the installation or a failure of outdoor air damper control coil freeze up may occur To avoid coil damage it is recommended to drain completely the non used coils or to fill them with an anti freeze soluti...

Страница 13: ...ctric heater must never operate without the ventilation 8 Electrical connections be imperatively connected to the control circuit of the motor The non respect of this instruction will cancel compulsorily the warranty on the motor Power supply cables entering into the unit must be run through cable glands mounted on unit panel All orifices for cable entry done on the panels must be sealed to preven...

Страница 14: ...electrical connections are tight and that the proper voltage is connected Belt alignment For a quick check make sure that the small rope touch each end of the pulleys as shown on drawing opposite Belt tensioning 90 5 kg 10 mm maxi 5 Check that all holes for cable entry are tightly sealed 6 Check tightness of setscrews on motors bearings and fans 7 Check alignment of fan and motor pulleys and belt ...

Страница 15: ...an pulley diameter 3 Securely tighten the set screw B on the flat surface of the pulley fixed sheave 4 Put on the belt and adjust its tension Do not force the belt on the pulley sheaves see paragraph Belt tensioning 5 The future adjustments should be performed by loosening the belt tension and by increasing or decreasing the pulley pitch diameter by half turns or full turns as required Re adjust t...

Страница 16: ...dusts it is recommended to clean them frequently If necessary comb the coil fins with an appropriate tool Care must be taken not to damage the fins while cleaning them The coils can be removed for cleaning as shown on the drawing below 10 4 Fan motor assembly There is no particular maintenance on fan motor assembly The units are equipped with permanently lubricated fan motor bearings It is not nec...

Страница 17: ... connections 10 Maintenance continued Step 2 Step 3 Step 4 10 6 Water quality It is not the manufacturer s policy to make recommendations in terms of water treatment please contact a specialised water treatment company However given the critical nature of this subject particular care should be taken to ensure that if treatment is required it works effectively Using untreated or unsuitable water le...

Страница 18: ...16 Notes ...

Страница 19: ...III ...

Страница 20: ...g product improvement programme our products are subject to change without prior notice Non contractual photos Dans un souci d amélioration constante nos produits peuvent être modifiés sans préavis Photos non contractuelles ...

Отзывы: