Automatic sauna splash system, type Sauna Plus 8 Basic
Index: 02
Date modified: 22/02/2022
OI No.: BA DW 010-02 Sauna Plus 8 Basic EN.docx
Page 22 of 36
In
Button operation
, the splash can also be triggered via an external control unit. For this purpose, instead
of the push button, the external control unit is connected via a potential-free contact.
6.3.2
Pause time/Locking time
If the
Cyclic operation
operation mode is set,
Pause time
is displayed here.
The pause time denotes the time period between splashes.
Set the desired pause time between the splashes.
If the
Button operation
operation mode is set,
Locking time
is displayed here.
The locking time denotes the time period during which no new splash can be started.
Set the desired locking time between the splashes.
No further splash is possible during the time period set here.
6.3.3
Water quantity
Set the duration of the water splash onto the sauna heater (opening time of the so-
lenoid valve)
6.3.4
Fragrance quantity
Set the run time of the fragrance dosing pump during the splash. The run time of the
fragrance quantity is limited to the set run time of the water quantity. This prevents
dosing of the pure fragrance onto the sauna heater.
6.3.5
Switch-on delay
After the voltage is switched on, the first splash will be delayed by the time period
set here.
6.3.6
Pump test
The fragrance dosing pump is activated for the displayed time period. Fragrance is
being dosed.
An attempt to start the pump test 2x in a row results in the following message: "After
pump test, rinse with MV test".
Now activate the MV test in the main menu so that the fragrance is flushed from the
line!