GRANUDOS 45/100 PLUS V70 Touch
Index: 03
Change date: 25.04.2018
Operating instructions no.: BA SW 001-03 Granudos 45-100 PL V70T.docx
Page 15 of 92
47.
Motor dust extraction
48.
Blower dust extraction
The chemicals are dissolved separately from each other in the dissolving system.
The control valve (44) opens when the starting level in the buffer tank has been
reached. The dissolving water is divided downstream of the motive water pump
(46). The particle stream is ducted via the float regulator valve (32) into the rinsing
tray (33). From there, it is sucked off by the injector (35) together with the
chemicals dosed in the rinsing pipe (34). The dissolving cyclone (40) circulates the
calcium hypochlorite granulate until it has completely been dissolved. An optical
sensor (41) detects the chlorine granulate dosed, which can be seen in the cyclone
shortly after the start of dosing. The controller reports a fault and the dosing is
interrupted when no chlorine is measured 8 seconds after the start of the 2nd
dosing cycle.
The following safety package is installed to ensure that chlorine granulate and acid
cannot mix and react with each other in the open part of the dissolving system:
The dosing of the two chemicals takes place in fixed cycles with pauses between
the dosing steps.
The power supplies of the two dosing motors are interlocked by a relay system
that ensures that
the two motors can never operate at the same time
!
The water supply and the water flow is monitored by pressure switches (31),
level switches (37) and flow switches (39).
Dosing only takes place when the water flow is ensured.
The dosing system is stopped and an appropriate fault message is generated
when a deviation from the set target values occurs.
ATTENTION !
The use of sulphuric acid up to a concentration of 50% is generally
possible. Changes in the dosing performance and/or increased
corrosiveness have to be considered when a higher concentration
Figure 5, Release device with option dust extraction
47
48