1 KEYPAD (HMI) AND BASIC PROGRAMMING 

1.1 INTEGRAL KEYPAD - HMI-CFW701

The integral keypad can be used to operate and program (view / edit all parameters) of the 
CFW701 inverter. There are two operation modes in the keypad: monitoring and programming. 
The key functions and display indications of the keypad may change according to the operation 
mode. The programming mode consists of three levels.

- Press this key to accelerate the motor up to the speed set in P0122. The motor speed is maintained 
while the key is pressed. When the key is released the motor decelerates up to its complete stop.
This function is active when all the following conditions are met:
1. Start/Stop = Stop.
2. General Enable = Active.
3. P0225 = 1 in LOC and/or P0228 = 1 in REM.

-  When in monitoring mode: press this key 

to decrease the speed.

-  When in programming mode, level 1: press 

this key to go to the next group.

-  When in programming mode, level 2: 

press this key to go back to the previous 
parameter.

-  When in programming mode, level 3: press 

this key to decrease the parameter value.

-  When in monitoring mode: press this key 

to enter in the programming mode.

-  When in programming mode, level 1: press 

this key to select the desired parameter 
group – it shows the parameters of the 
selected group.

-  When in programming mode, level 2: press 

this key to show the parameter – it shows 
the parameter value for its modification.

-  When in programming mode, level 3: press 

this key to save the new parameter value 
– it returns to level 2 of the programming 
mode.

-  Press this key to accelerate the motor 

according to the acceleration ramp time.

  This option is active when:
  P0224 = 0 in LOC and/or
  P0227 = 0 in REM.

-  Press this key to decelerate the motor 

according to the deceleration ramp time.

  This option is active when:
  P0224 = 0 in LOC and/or
  P0227 = 0 in REM.

-  When in monitoring mode: press 

this key to increase the speed.

-  When in programming mode, level 

1: press this key to go back to the 
previous group.

-  When in programming mode, level 

2: press this key to go to the next 
parameter.

-  When in programming mode, level 

3: press this key to increase the 
parameter value.

-  When in programming mode, level 

1: press this key to go back to the 
monitoring mode.

-  When in programming mode, level 

2: press this key to go back to the 
level 1.

-  When in programming mode, level 

3: press this key to cancel the new 
value (the value will not be saved) 
and it will return to level 2 of the 
programming mode.

-  Press this key to define the motor 

rotation.

  This option is active when:
  P0223 = 2 or 3 in LOC and/or 

P0226 = 2 or 3 in REM.

-  Press this key to change between 

LOCAL and REMOTE mode.

  This option is active when:
  P0220 = 2 or 3.

USB communication port 

(1)

(1)

 Available from the serial number 1023801859.

Figure 1.1:

 Operator keys