43
Safety Interlocks electromagnetic / Safety Switch with interlocking function
System Status
Magnet
Activation
LED
Safety
Outputs
Signal
Output
“Mag”
Green
Red
Yellow
OSSD 1,
OSSD 2
Signal
Door open
0 V
On
Off
Off
0 V
0 V
Door closed, actuator in contact
0 V
On
Off
Blinks
0 V
24 V
Door closed and locked
24 V
On
Off
On
24 V
24 V
Lock cannot be closed.
Door not correctly closed
or magnet contaminated
24 V
On
Off
Blinks
0 V
0 V
Error warning
1)
, door locked
24 V
On
Blinks
2)
On
24 V
0 V
Error
0 V / 24 V
On
Blinks
2)
Off
0 V
0 V
Forcible separation of the guard
locking device and the actuator
3)
24 V
On
Blinks
2)
Blinks
2)
0 V
0 V
Table 3: Diagnostic function of SD4ICS0xSE89 variant "guard locking device monitored"
System Status
Magnet
Activation
LED
Safety
Outputs
OSSD 1,
OSSD 2
“Mag”
Green
Red
Yellow
OSSD 1,
OSSD 2
Signal
Door open
0 V
On
Off
Off
0 V
0 V
Safety guard closed, actuator
in,safety guard can be locked
0 V
On
Off
Blinks
24 V
24 V
Door closed and locked
24 V
On
Off
On
24 V
24 V
Lock cannot be closed.
Door not correctly closed
or magnet contaminated
24 V
On
Off
Off
0 V
0 V
Error warning
1)
, actuator in
0 V/24 V
On
Blinks
2)
Blinks/
On
24 V
0 V
Error
0 V/24 V
On
Blinks
2)
Off
0 V
0 V
Table 4: Diagnostic function of SD4ICS1xSE89 variant "Actuator monitored"
1)
After 30 minutes
error
2)
See blink code, table 2
3)
See note in section
„6.3. Forcible Separation of the Guard Locking Device and the Actuator“