USING THE GENERATOR
NOTE:
When operating a single generator, DO NOT exceed
15A
(1800 running watts) on the NEMA 5-20 re-
ceptacles. The NEMA 5-20R capable of connecting devices up to 20A ONLY when two generators are paral-
lel connected (see “PARALLEL OPERATION”).
Low Oil Indicator
Overload Indicator
Output Indicator
AC 120V Duplex
NEMA 5-20R
DC 5V USB Outlet
1A (top)/2.1A (bottom)
Grounding Nut
Parallel Connection Ports
Manual Shut-Off
Switch
3-in-1 Dial Switch
(CHOKE, RUN, OFF)
Overload
Reset Button
Eco-Mode Switch
ECO-MODE
ON
OFF
MANUAL
SHUT OFF
CHOKE
PARALLEL CONNECT
RESET
AC 120V
GROUNDING
DC 5V
RUN
OFF
KNOW YOUR CONTROL PANEL
Become familiar with the functions and capacity of each component on the control panel.
ECO-MODE SWITCH
This generator is equipped with an Eco-Mode Idle Control Switch. Engaging this switch allows the system to
regulate the engine speed and automatically adjust its fuel consumption to match the required load. When
the electrical load changes, the generator engine will automatically speed up and slow down as needed. This
reduces fuel consumption and noise levels, while extending runtime and engine’s lifespan.
Keep this switch engaged ONLY when the power load requirement is LESS THAN
1350W
(75% of the rated
watts). Do not engage the Eco-Mode Switch when the total load is more than 1350W. The generator engine
must run at full speed to supply power for anything over 1350W.
Fig. 12 - Control Panel