130
Findings
Comments
The inlet of the harvest valve
is cool enough to touch and
the compressor discharge
line is hot.
Cppl & Hpt
This is normal as the discharge
line should always be too hot to
touch and the harvest valve inlet,
although too hot to touch during
harvest, should be cool enough
to touch after 5 minutes into the
freeze cycle.
The inlet of the harvest
valve is hot and approaches
the temperature of a hot
compressor discharge line.
Hpt & Hpt
This is an indication something is
wrong, as the harvest valve inlet
did not cool down during the
freeze cycle. If the compressor
dome is also entirely hot, the
problem is not a harvest valve
leaking, but rather something
causing the compressor (and the
entire ice machine) to get hot.
Both the inlet of the harvest
valve and the compressor
discharge line are cool
enough to touch.
Cppl & Cppl
This is an indication something is
wrong, causing the compressor
discharge line to be cool to the
touch. This is not caused by a
harvest valve leaking.
Содержание Manitowoc NEO UDP0080A
Страница 2: ......
Страница 18: ...18 Part Number STH098 06 19 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 74: ...74 Part Number STH098 06 19 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 166: ...166 Part Number STH098 06 19 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 176: ...176 Part Number STH098 06 19 ELECTRONIC CONTROL BOARD UDP0080 1 2 3 4 5 6 7 8 9 10...
Страница 179: ......