Terminal
rail
Terminal
Connection
Explanation
X1.3
PE / 1 / 2 / 3
Connection of outdoor unit
230 V, 1~, N, 50 Hz
PE / 4 / 5
Supply additional heating circuit (op-
tional)
230 V, 1~, N, 50 Hz
6
Load contactor hot water flange heat-
ing (optional)
230 V
Relay output
7
Error output H5 (optional)
230 V output
8
Contact utility lock (optional)
Switch against "9 Earth", with potential
free contact.
If contact closed:
▪
compressor out of operation,
▪
pumps switched off,
▪
second heat exchanger switched off.
9
Earth (optional)
10
Heating/cooling thermostat (optional)
Switch against "9 Earth", with potential
free contact.
If contact closed:
▪
Heating or cooling operation inter-
rupted,
▪
heating circuit pump switched off,
DHW supply possible.
11
Boiler change-over (optional)
Switch against "9 Earth", with potential
free contact - see expert level/
add.HE/add. heat exchanger (parame-
ter 602).
If contact closed:
▪
When selecting additional heat ex-
changer boiler the compressor is
switched off. Heating circuit and do-
mestic water feeder pumps remain in
operation.
▪
When selecting additional heat ex-
changer electric heating the contact
becomes ineffective.
12
Heating/cooling (optional)
Switch against "9 Earth", with potential
free contact.
Change-over between heating and cool-
ing via external access.
13
DHW thermostat (optional)
Switch against "9 Earth", with potential
free contact.
If contact closed:
▪
DHW supply
(no water sensor B3 connected),
▪
DHW supply blocked
(if DHW sensor B3 connected).
14 / 15
DHW sensor B3 (optional)
NTC 10 k
Ω
16 / 17
eBus remote control station (optional) Terminal 16 on eBus-
Terminal 17 on eBus+
18 / 19 / 20
RS485-Bus add. heating circuit (op-
tional)
(1
Optional connection L2 only for WWP L 11 AERS-HE and WWP L 15 ARS-HE, when using the second stage
electric heating.
Installation and operating instruction
Hydraulic unit WWP L 7 ... L 15
5 Installation
83279602 • 1/2014-05 • La
31-59