4.9 Flue gas connection
Flue gas lines approved by planning law
The WTC is equipped with a concentric flue gas
connection Ø 125/80 located at the top of the unit. The
flue gases should be extracted via temperature and
corrosion resistant flue gas duct:
•
in vertical ducting
•
via external wall connections
•
for roof heating centres with vertical flue gas duct
•
air-flue gas chimney
The combustion air can be introduced:
•
from the boiler room (room air dependent operation)
•
by concentric pipe systems
(room air independent operation)
•
by non-closing supply air ducts
Only CE certificated or locally tested and approved flue
gas systems must be used.
The Weishaupt Flue gas - air - system WAL-PP,
see installation and operating manual WAL-PP, offers
approved kits and individual components.
The flue gas duct must be gas tight.
☞
Carry out soundness test.
Note:
If a
plastic
flue gas system is connected,
which is approved for flue gas temperatures
up to 80°C, the maximum flue gas
temperature must be set to 80°C. Use
parameter P33 (see Ch. 6.3.3). The
Weishaupt flue gas-air system WAL-PP is
approved for temperatures up to 120°C.
Flue gas connection
1
Boiler connection piece
2
Test point in the supply air aperture
3
Flue gas sampling point
1
2
3