Des.
Parameter
WTC 45
WTC 60
Unit
A1
Heating controller P ratio
130
130
x0.25
A2
Heating controller I ratio
3
3
x0.125s
A3
Heating controller D ratio
32
32
x0.032s
A4
A5
A6
A7
Max. temperature range
➩
Ch. 8.1
45
45
K
Safety temperature (STL) flue gas temperature
A8
Boiler rating at ignition
73
73
%
A9
Max. temperature gradient flow
3,0
3,0
K/s
A10
Max. fan speed
5460
–
rpm
–
4950
A11
Boiler rating delayed heating operation
➩
Ch. 7
27
26
%
A12
Water pressure monitor
1
1
A13
Max. differential temperature
➩
Ch. 8.1
28
28
K
Flow temperature - safety temperature (STL)
44
6
0
12
24
Fr 03.
Nov 06
11:25
Raumte
mp
20°C
Heizpr
ogramm
1
12
03.Nov
0
mp
20°
ogramm
1
2
2
3.Nov 0
6
20°C
amm 1
1
Service software WCM diagnostic
Most of the control and limit value parameters relating to
the system can be set via the heating engineer level. In
rare cases it may be necessary to adapt the condensing
boiler to the heating system using these system
parameters.
The Software WCM Diagnostic is required to carry out
this process. The use of the Software and a detailed
description of the system parameters can be found in the
user instructions of the Software.
6.4.1 Special system parameters
Parameters marked in this way are safety
relevant for the operation of the system.
Changes are only permitted following
discussions and approval from Weishaupt
service department.
6.4 Service functions via PC interface
The Weishaupt Condens Manager (WCM) is equipped
with an interface for PC connection. Data transfer is
carried out via Weishaupt eBUS adapter (W-EA) from
eBUS via RS 232 interface to PC.
The W-EA, as well as the Service Software WCM
Diagnostic are available as accessories.
Your PC should meet the following requirements:
•
Processor from 400 MHZ
•
Operating system WINDOWS 95 or higher
•
RAM
≥
64 MB
•
Resolution (screen/grafics card): 800 x 600 Pixel
The software makes the following functions available:
•
Display of operating conditions of burner, fan, pump
and gas valve.
•
Display of temperatures, speeds, ionisation current,
as well as other setpoints and actual values.
•
Graphic display of boiler and system data for longer
periods of time.
•
Evaluation of system records with error statistics.
•
Parameter setting of special system parameters.
Telephone Network
Mobile Network