6.2.2 Service level
The service level gives information about:
Actuator position of the individual operating points,
the most recent fault,
flame signal during burner operation.
Press [Enter] for approx. 2 seconds.
The service level is activated.
Press [Enter] to reach the next information.
Only in conjunction with variable speed drive
The speed set can be displayed at information
0
…
9
.
Displaying the fan speed:
Press key [L/A].
No.
Information
0
Actuator position in operating point P
0
1
Actuator position in operating point P
1
2
Actuator position in operating point P
2
(switch off point stage 2 when running closed)
3
Actuator position in operating point P
3
(switch on point stage 2 when running open)
9
Actuator position in operating point P
9
10
…
18
Fault memory
most recent fault … ninth last occurred fault
Display additional information:
1. Detailed error codes / operating status:
Press [+] key.
2. Detailed error codes:
Press [–] and [+] keys simultaneously.
Repetition counter:
Press key [G].
19
Flame Signal
Left display
(1
:
Alternating value
Right display:
Flame quality
minimum value: >
10
recommended value: >
15
–––
: no flame
(see also error code
68h
)
Flame sensor QRB4
(2
Flame sensor for continuous op-
eration
255
…
121
: no flame
30
: high quality
recommended value: <
40
Values on request.
(1
Only in conjunction with continuous operation. No evaluation is carried out with intermittent operation.
(2
Flame sensor QRB4 is not suitable for continuous operation.
After information
19
or a waiting time of approx. 20 seconds the combustion man-
ager changes over to the operating level.
Содержание WL40Z-A 1LN
Страница 1: ...Installation and operating instruction Oil burner WL40Z A 1LN 83298902 2 2019 05 ...
Страница 91: ...Installation and operating instruction Oil burner WL40Z A 1LN 12 Project planning 83298902 2 2019 05 La 91 112 ...
Страница 106: ...Installation and operating instruction Oil burner WL40Z A 1LN 14 Notes 83298902 2 2019 05 La 106 112 14 Notes ...
Страница 107: ...Installation and operating instruction Oil burner WL40Z A 1LN 14 Notes 83298902 2 2019 05 La 107 112 ...
Страница 111: ...83298902 2 2019 05 La ...