Installation-  and maintenance instruction

B40A

Содержание B40A

Страница 1: ...1 171 615 82 05 01 Installation and maintenance instruction B40A...

Страница 2: ...178 004 53...

Страница 3: ...itionelectrodes 4 Nozzleassembly 5 Ignition cable 6 Ignition transformer 7 Photo cell 8 Controlbox 9 Resetbutton 10 Cover inspection glass 11 Fanwheel 12 Motor 13 Nozzleassemblyadjustment 14 Blasttube...

Страница 4: ...alue of 11 86 kWh kg for light oil has been used Note that the spray angle and the spray pattern change with the pump pressure 195 400 B 420 200 230 DIMENSIONS RECOMMENDED NOZZLE Because of different...

Страница 5: ...carried out in accordance with local regulations The installer of the burner mustthereforebeawareofallregulations relating to oil and combustion Onlyoilsuitablefortheburnershouldbe used and then in c...

Страница 6: ...at the main switch and cut off the oil supply Open the cover and disconnect the connecting pipe by loosening screw A 1 Loosen or swing out the burner from the boiler 2 Loosen 2 fixing screws and with...

Страница 7: ...re starts Post ignition 2 If a post igniton of 15 s is wanted move the ignition transformer from terminal 7 to terminal 6 LOA24 173 LIST OF COMPONENTS A1 Oil burner control R1 Photoresistor A2 Twinthe...

Страница 8: ...disregarded The tables do not include any lengths exceeding 100 m as experience shows that longer lengths are not needed Thetablesapplytoastandardfueloilof normal commercial quality according to curr...

Страница 9: ...closedandbecause of the full speed of the gear set the pressure necessary to open the valve will be built up very rapidly AS Solenoid valve with cut off Gear set capacity see pump capacity curves C 67...

Страница 10: ...79 7 97 94 81 2 00 6 65 79 68 7 06 84 72 7 45 88 76 7 81 93 80 8 18 97 83 8 49 101 86 8 81 104 90 9 12 108 93 2 25 7 49 89 76 7 94 94 81 8 38 99 85 8 78 104 89 9 18 109 94 9 55 113 97 9 91 117 101 10...

Страница 11: ...not reset Appliance overheat device has operated Control relay or photocell defective Adjust thermostat Check by replacement Motor runs Burner runs to lockout No oil being delivered Excessive flue dr...

Страница 12: ...ument s following the provisions of Directive if applicable Place and date of issue name and signature of equivalent marking of authorized person DECLARATION OF CONFORMITY BENTONE BENTONE Ulf Bondeson...

Страница 13: ...10 1 4 3 0 3465 0 2 to 1 1 CE 0036 0134 98 16 6 35 6 03 09 93 to 0 25 B 10KA 2 0 4 6 3778 0 2 to 0 95 CE 0036 0135 98 23 7 54 5 18 10 96 to 0 1 B 10ZHV 1 2 2 5 3525 0 2 to 1 0 CE 0036 0136 98 14 2 29...

Страница 14: ...0 3592 0 2 to 9 25 CE 0036 0148 98 142 2 699 2 10 11 94 to 0 1 B 60 2F 20 0 90 0 3466 0 3 to 11 4 CE 0036 0149 98 237 0 1066 5 03 09 93 to 0 8 B 60 3F 20 0 90 0 3591 0 3 to 11 4 CE 0036 0150 98 237 0...