6.2.4 Access level
In the access level, the configuration can be adapted relative to the burner type or
version.
In the parameter level, the display mode must be configured to
1
, to enable access
to parameters E0 … E3 [ch. 6.2.3].
Press [G] and [L/A] simultaneously.
The access level is activated.
Press [+] key.
Parameter
E0
is displayed.
Press and hold [Enter] key and set the parameter using [+] or [–].
Press [+] to reach the next parameter.
Parameters Information
Setting range
E0
Burner type
0
: single fuel burner
1
: dual fue burner
E1
Operating mode
(display only, no adjust-
ment possible)
0
: intermittent operation
1
: continuous operation
E2
Flame sensor type
0
: ionisation electrode / flame sensor FLW
1
: switch input (X3:14)
2
: flame sensor QRB
E3
Fan configuration
0
: Off
1
: fan control
2
: fan control with fan monitoring
3
: VSD
4
: fan control according to modulating degree specified
5
: DAU control
6
…
255
: off