Installation and operating instruction
Gas burner WG10…/0-D ZM-LN
7 Commissioning
83300902 1/2019-02 La
40-112
7.1.1 Connect measuring devices
Measuring device for ionisation current
Remove ionisation cable from the plug coupling.
Connect current measuring device in series.
Ionisation current
Extraneous light detection from
1 μA
Minimum ionisation current
5 μA
Recommended ionisation current
9 … 15 μA
Pressure measuring device for mixing pressure
Open pressure test point for mixing pressure
1
and connect pressure measur-
ing device.
1