background image

©

2019 WEINZIERL ENGINEERING GmbH 

Page 7/8

 

C. 

Function 1 

– 16 (Timer / Logic) 

 

 

 

 

 

 

These parameters set the additional functions such as timer and 
logic. The logic gate truth tables can be found in the device 
menu section. 

Function type (Disabled) 

If set to ‘Disabled’, no timer specific parameter and group object 
is available. 

Function type (Timer) 

The timer specific parameters and group objects are available. 

Function name (free text input) 

The function name can be chosen freely. The maximum length of 
the name is 10 characters. 
The name will be shown in the group object entry within the ETS 
software. After the ETS application download the name will be 
shown within the devices function menu entry as well as in the 
function submenu as a headline. 

Timer type (Switch-on delay) 

A timer that switches ON after duration defined in 
‘Delay time [s]’ parameter. 
The output value can be inverted by parameter  
‘Output’ (Not inverted / Inverted). 

Input 

-------1------------------0----------

 

Output 

-------|-T-1--------------0----------

 

 

Timer type (Switch-off delay) 

A timer that switches OFF after duration defined in 
‘Delay time [s]’ parameter. 
The output value can be inverted by parameter  
‘Output’. (Not inverted / Inverted) 

Input 

-------1------------------0----------

 

Output 

-------1------------------|-T-0------

 

 

 

 

 

Timer type (Switch-on and -off delay) 

A timer that switches ON and OFF after duration defined in 
‘Delay time [s]’ parameter. 
The output value can be inverted by parameter  
‘Output’. (Not inverted / Inverted) 

Input

 

-------1------------------0----------

 

Output

 

-------|-T-1--------------|-T-0------

 

 

Timer type (Impulse (Staircase)) 

Timer with impulse that 

– after being switched 

ON

 

– 

automati-

cally switches OFF

 after a defined duration defined in 

‘Delay time [s]’ parameter. 
The output value can be inverted by parameter  
‘Output’. (Not inverted / Inverted) 

Input

 

-------1------------------0----------

 

Output

 

-------1-T-0-------------------------

 

 

 

Each timer can be stopped by sending the opposite val-
ue to its input group object. For example:  
An already started switch on timer can be stopped by 
sending OFF (0) to its input group object. 
 

Function type (Logic) 

The logic specific parameters and group objects are available. 

 

Function name (free text input) 

The function name can be chosen freely. The maximum length of 
the name is 10 characters. 
The name will be shown in the group object entry within the ETS 
software. After the ETS application download the name will be 
shown within the devices function menu entry as well as in the 
function submenu as a headline. 

Gate type (AND gate) 

The output is triggered on (1), if both inputs are switched on (1). 

Gate type (OR gate) 

The output is triggered on (1), if one or both inputs are switched 
on (1). 

Group Object 

Type KNX 

Size 

Direction 

Timer 

– Switch-on delayed - Input 

1.002 

1 Bit 

From KNX 

Timer 

– Switch-on delayed - Output 

1.002 

1 Bit 

To KNX 

Group Object 

Type KNX 

Size 

Direction 

Timer 

– Switch-off delayed - Input 

1.002 

1 Bit 

From KNX 

Timer 

– Switch-off delayed - Output 

1.002 

1 Bit 

To KNX 

Group Object 

Type KNX 

Size 

Direction 

Timer 

– Switch-on/off delayed - Input 

1.002 

1 Bit 

From KNX 

Timer 

– Switch-on/off delayed - Output 

1.002 

1 Bit 

To KNX 

Group Object 

Type KNX  Size 

Direction 

Timer 

– Switch-impulse (staircase) - Input 

1.002 

1 Bit 

From KNX 

Timer 

– Switch-impulse (staircase) - Output 

1.002 

1 Bit 

To KNX 

Group Object 

Type KNX  Size 

Direction 

Logic 

– Gate input A - Input 

1.002 

1 Bit 

From KNX 

Logic 

– Gate input B - Input 

1.002 

1 Bit 

From KNX 

Logic 

– Gate output – Output 

1.002 

1 Bit 

To KNX 

 

 

Содержание KNX PowerSupply USB 367

Страница 1: ...ly KNX devices for the medium twisted pair The integrated bus choke separates the DC supply voltage from the bus signals Output auxiliary voltage 30 V This output is used to supply additional equipment The output is galvanically connected to the bus voltage but is not at the same potential This means that minus bus and minus of the auxil iary voltage are not the same and must not be connected to e...

Страница 2: ... line of Weinzierl via a group object See parameter section for details Local download via USB The internal application can be loaded both with an additional interface via the KNX bus or locally via the integrated USB inter face When using an additional interface the download is done conventionally but there may not be any USB connection on KNX Power Supply USB 367 For local download via the integ...

Страница 3: ...f the KNX voltage The default reset time is 30 seconds To stop the count down press escape G Submenu System Info This submenu displays information about the device serial number SN App ID App status App ST and Firm ware Revision Fw Rev H Sub menu Counters The operating status is logged automatically in the device and can be viewed in this sub menu All times as displayed in the format h m Operation...

Страница 4: ... start To stop countdown press en ter again during countdown N Timer Switch on and off delay Timer that switches ON OFF after de fined duration in seconds set via the ETS After pressing enter count down will start and the timer will turn on After first countdown is finished press enter again to start countdown to turn off To stop countdown press enter again during countdown O Timer Impulse Stairca...

Страница 5: ...er appears Each Weinzierl device with a display of this product range pro vides this parameter As soon as the device wakes up the asso ciated group telegram will be sent to the KNX bus which wakes up every other device whose display synchronization group object is associated to the same group address Operating control Enabled Disabled If enabled a parameter Cycle time 10 s 24 h and a group object ...

Страница 6: ...cs values will be sent to the bus If Reset max values is triggered the values of diagnostic ob jects Current max and Temperature max are reset to the actual values and sent to the bus for confirmation B Alarm This parameter sets basic alarm functions Send alarm Disabled No group object for alarm states are available Send alarm On alarm On alarm and alarm end If activated the alarm state group obje...

Страница 7: ... duration defined in Delay time s parameter The output value can be inverted by parameter Output Not inverted Inverted Input 1 0 Output 1 T 0 Each timer can be stopped by sending the opposite val ue to its input group object For example An already started switch on timer can be stopped by sending OFF 0 to its input group object Function type Logic The logic specific parameters and group objects ar...

Страница 8: ...which is used by ETS is 55 This length has been specified as require ment for new KNX system devices An APDU length of 55 results in total length of a KNX telegram on twisted pair of 64 bytes and occupies the bus for about 90 ms The download is much faster if the USB interface is in stalled in the same line as the target device With each line coupler in between the download time growths Group Obje...

Отзывы: