background image

©

2019 WEINZIERL ENGINEERING GmbH 

Page 1/15

 

 

Operation and installation manual

 

KNX IO 511 (1O2I)

 

(Art. # 5232)  

Switching actuator with 1 output and 2 binary inputs 
 

 

 

KNX IO 511 (1O2I) 

 
Application 

The KNX IO 511 (1O2I) is a compact switching actuator with 1 
bi-stable output and 2 binary inputs. The actuator provides the 
function for universal outputs including scene control, timer, 
staircase lighting and heating valves (PWM for thermoelectric 
valve drives).  

The inputs can be connected to conventional switches with an 
external voltage of 12 to 230 V. In ex-factory settings the inputs 
are connected internally to the actuator. The actuator combined 
with input B1 serves as a latching relay. Input B2 is used for zero 
crossing detection.  

Two push buttons and three LEDs allow a local operation and a 
visualization of the device state. 

In addition to the output and input channels the device includes 
16 independent functions for logic or timer control. 
 

1.  Installation and Connection 

The KNX IO 511 (1O2I) is designed for installation on a DIN rail 
(35 mm) with a width of 1 unit (18 mm). An installation-friendly 
design with pluggable screw terminals helps to reduce the cost 
of commissioning. It features the following controls and displays: 

 

 

 
 
 
 
 
 
 
 
 

 

This device is powered by the KNX bus. An external power 
supply is not necessary. 

 
 The device is not working without bus power.

 

A. 

KNX Programming mode 

 
The KNX programming mode is activated/deactivated either by 
pressing the flushed KNX programming button 

❸ 

or by simulta-

neously pressing the buttons 

❼ 

and 

.

 

Accessing the pro-

gramming mode via the device front buttons can be enabled / 
disabled via the ETS® by changing the value of 

Prog. mode on 

device front.

 

When the programming mode is active, the programming LED 

❷ 

and LED Ch/M 

 light red. 

 

B. 

Manual operation and status display 

The LED Ch/M 

 

lights up or flashes if the device is successful-

ly powered by the KNX bus.  

By pressing button A 

 long, the manual operation mode will 

be entered for channel (A). This is indicated by cyclic single 
flashing of LED Ch/M 

 in orange. 

The actuator (channel A) can be switched on with button On 

 

and switched off with button Off 

. The manual operation mode 

can be exit by pressing the buttons (Esc) 

 

und

 

 simultane-

ously. 

The LED A 

 is used to display the status of the channel (A). It 

lights when the channel is on and is switched off when the chan-
nel is off.  

By pressing button B 

 long, the manual operation mode will 

be entered for channel pair B (Ch B In1/In2).This is indicated by 
cyclic double flashing of LED Ch/M 

 in orange. 

If manual operation of channel pair B is activated, the bus tele-
grams of In1 and In2 can be triggered by button 1 

 and 2 

if input channel is configured by ETS.  

LED 1 

 and LED 2 

 are used to indicate state of selected 

channel pair while manual operation. They light green when the 
button 1 

❼ 

or

 

❽ 

is pressed. 

The manual operation mode can be exit by pressing the buttons 
(Esc) 

 

und

 

 simultaneously. 

Summary of the states of LED Ch/M 

 

LED Status 

Meaning 

LED lights green 

Device is working in standard operation mode. 

LED lights red 

Programming mode is active. 

LED flashes 1x orange 
 

Programming mode is not active. 
Manual operation is active. 
Switching first channel (A) 

LED flashes 2x orange 
 

Programming mode is not active. 
Manual operation is active. 
Switching channel pair (B In1/In2) 

LED blinks red 

Programming mode is not active. 
Manual operation is not active. 
The device is not properly loaded e.g.  
after an interrupted download. 

LED blinks green 

The device is currently loaded by the ETS. 

EN 

 KNX bus connector 

 

Programming LED 

 

Button f. programming mode 

 LED On/1 (multicolor) 

 LED Ch/M (multicolor) 

 LED --/2 (multicolor) 

 Button A (On/1) 

 Button B (Off/2) 

 Pluggable screw terminals 

 
 

 

 

 

Содержание KNX IO 511

Страница 1: ...and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is successful ly powered by the KNX bus By pressing button A long the manual operation mode will be entered for channel A This is indicated by cyclic single flashing of LED Ch M in orange The actuator channel A can be switched on with button On and switched off with button Off The manual op...

Страница 2: ... settings It is possible to reset the device to its factory settings Disconnect the KNX Bus connector from device Press the KNX programming button and keep it pressed down Reconnect the KNX Bus connector of device Keep the KNX programming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 4 Wiring sch...

Страница 3: ... expiry of the time limit or manually the last state of the outputs remains until a new switching telegram is received again The following options are selectable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit Heartbeat Cyclic sending of values to the KNX Bus to indicate that the device is operational For the Cycle tim...

Страница 4: ...r to prevent unmeant switching Nevertheless the individual lamps can controlled by use of the priority object without cancel ing the lock F Lock function Polarity of object This parameter defines if the lock should be activated by receiv ing a 1 or by receiving a 0 The following options are selectable Lock active on 1 Lock active on 0 Behavior on start This parameter configures which state the out...

Страница 5: ...e The duration of the switch off delay is configured in this parame ter Input 1 0 Output 1 T 0 Retriggerable If these parameters are activated the respective delay time is restarted upon receipt of the corresponding switching signal Function Staircase function If the staircase function is selected on the parameter page Ac tuator 1 General a group object for the staircase function appears in additi...

Страница 6: ...control value is expressed in percent and defines the period during which the output is switched on in one cycle Example Cyclic time 10 Min Maximum control value PWM 80 Maximal output state ON 8 min OFF 2 min Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enab...

Страница 7: ... the lock is activated this value can be set with this parameter L Input B1 General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group objects are named Input with the channel number which ...

Страница 8: ...telegram can be configured here which is sent when the lock is deactivated O Function Impulse counter If the impulse counter function is selected further parameters are displayed in the general settings of the input channel Here the general settings of the impulse counter are made a scaled counter and or counter of the rate of change must also be se lected Input signal Here it can be selected whet...

Страница 9: ...it To KNX Shutter function The Shutter function parameter determines whether only one shutter direction or 1 button control is to be used Up Step Stop Down Step Stop Toggle direction User control The parameter User control determines the sending of tele grams on short and long button press Long Drive Short Step Stop Long button press Drive command via object 21 Short button press Stop step command...

Страница 10: ... button press the configured delay time is started Starting with the first scene position the next scene position of the list is sent with each short button press after the last scene position has been sent the list starts again from the beginning After the delay time has expired the list starts again at the first scene position on the next short button press When the lock function is used the sce...

Страница 11: ...t and continue Counter value is reset to 0 and continues in creasing on ever pulse Counter stop Counter value stays on limit value and must be reset by object Send on device restart It can be determined with this parameter whether the counter value should be sent when the device is restarted Reset via object If this function is activated the following object appears Group Object Type KNX Size Dire...

Страница 12: ...ameter is displayed to select the min imal delta from the last sent value for sending a new counter value Cyclically An additional parameter is displayed to configure the sending frequency of the counter variable On change and cyclically Both sending conditions are active Monitoring limit value When limit monitoring is activated the following object is dis played Group Object Type KNX Size Directi...

Страница 13: ... as the input of the next function Y Function 1 16 Timer Function name 10 Characters The function name can be chosen freely The name is visible in the group object entry in the ETS soft ware This makes it easier to work with the associated group objects because the given name is displayed there as a label Timer type Switch on delay A timer that switches ON after duration defined in Delay time s pa...

Страница 14: ... type AND gate The output is triggered on 1 if both inputs are switched on 1 Gate type OR gate The output is triggered on 1 if one or both inputs are switched on 1 Gate type XOR gate The output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are...

Страница 15: ...idered The device is a permanently connected equipment A readily accessible disconnect device shall be in corporated external to the equipment The installation requires a 16 A fuse for external overcurrent protection The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 511 ets4 Datasheet www weinzierl de en products 511 datasheet CE Declaration www ...