Send state
This parameter defines the behavior of the state objects:
-
Disabled
State objects are deactivated and not displayed
-
Only on read
State objects send only on request
-
On change
State objects send on value change
-
Cyclic and on change
State objects send cyclically and on value change
Group Object
Type KNX
Size
Direction
GO 18 Actuator 1: Output - State
1.001
1 Bit
To KNX
GO 19 Actuator 1: Valve actuator (PWM)
– State*
5.001
1 Byte
To KNX
* if valve actuator was selected
Time for cyclic state
Is selected state object
“Cyclic and on change“, in this parameter
the cycle time can be set.
Lock function
With this parameter the lock function can be enabled. If this
functionality is activated, the associated group objects as well as
the paramet
er page “Actuator 1: Lock function” are displayed for
further configuration. If the lock has been activated via the group
object "Lock", the received switching telegrams are not execut-
ed.
In addition to the lock object, there is also a priority object, which
can be switched independently of the lock. Thus, it is possible to
set an output state without affecting other functions.
Group Object
Type KNX
Size
Direction
GO 15 Actuator 1: Lock - Activate
1.001
1 Bit
From KNX
GO 16 Actuator 1: Prior. output - Switch
1.001
1 Bit
From KNX
Example of the priority object:
In the case of events in public buildings or in restaurants, the
normal operation can be set into an inoperative state by the lock
group object. Thus it is possible to lock during the lecture or
concert, switches that are accessible to unauthorized persons, in
order to prevent unmeant switching. Nevertheless, the individual
lamps can controlled by use of the priority object without cancel-
ing the lock.
F.
Lock function:
Polarity of object
This parameter defines, if the lock should be activated by receiv-
ing a 1 or by receiving a 0.
The following options are selectable:
-
Lock active on 1
-
Lock active on 0
Behavior on start
This parameter configures, which state the output should set, if
the lock activates.
The following options are selectable:
-
No reaction
-
Switch on
-
Switch of
This output state can still be changed by the priority object.
Behavior at end
This parameter defines, which state the output should set, if the
lock deactivates.
The following options are selectable:
-
No reaction
-
Switch on
-
Switch off
-
State before lock
-
State without lock
State before lock:
This restores the original state before the lock was activated.
Switching telegrams received during the lock are ignored.
State without lock:
Here the state of the last received switching telegram is restored.
This takes into account the received switching telegrams during
the lock. Thus, when the lock is deactivated, the last received
switching telegram is set.
Function (Universal output)
If the universal output is selected on the parameter page "Actua-
tor 1: General", the actuator can be used as a switching output.
A parameter for the scene function is also displayed.
Group Object
Type KNX
Size
Direction
GO 11 Actuator 1: Output - Switch
1.001
1 Bit
From KNX
Scene function
With this parameter the scene function can be enabled or disa-
bled. If this functionality is enabled, the respective group object
as well as the parameter page "Actuator 1: Scene function" are
displayed for further configuration of scenes 1-16.
Group Object
Type KNX
Size
Direction
GO 12 Actuator 1: Scene
– Activ./Lrn.
18.001
1 Bit
From KNX