Send state 

This parameter defines the behavior of the state objects: 

Disabled 
State objects are deactivated and not displayed 

Only on read 
State objects send only on request 

On change 
State objects send on value change 

Cyclic and on change 
State objects send cyclically and on value change 

Group Object 

Type KNX 

Size 

Direction 

GO 18 Actuator 1: Output - State 

1.001 

1 Bit 

To KNX 

GO 19 Actuator 1: Valve actuator (PWM) 
– State* 

5.001 

1 Byte 

To KNX 

* if valve actuator was selected  
 

Time for cyclic state 

Is selected state object 

“Cyclic and on change“, in this parameter 

the cycle time can be set. 

Lock function 

With this parameter the lock function can be enabled. If this 
functionality is activated, the associated group objects as well as 
the paramet

er page “Actuator 1: Lock function” are displayed for 

further configuration. If the lock has been activated via the group 
object "Lock", the received switching telegrams are not execut-
ed.  

In addition to the lock object, there is also a priority object, which 
can be switched independently of the lock. Thus, it is possible to 
set an output state without affecting other functions. 

Group Object 

Type KNX 

Size 

Direction 

GO 15 Actuator 1: Lock - Activate 

1.001 

1 Bit 

From KNX 

GO 16 Actuator 1: Prior. output - Switch 

1.001 

1 Bit 

From KNX 

 

 

Example of the priority object: 
In the case of events in public buildings or in restaurants, the 
normal operation can be set into an inoperative state by the lock 
group object. Thus it is possible to lock during the lecture or 
concert, switches that are accessible to unauthorized persons, in 
order to prevent unmeant switching. Nevertheless, the individual 
lamps can controlled by use of the priority object without cancel-
ing the lock. 
 

F. 

Lock function: 

 

 

 

Polarity of object 

This parameter defines, if the lock should be activated by receiv-
ing a 1 or by receiving a 0.  

 
The following options are selectable: 

Lock active on 1 

Lock active on 0 

Behavior on start 

This parameter configures, which state the output should set, if 
the lock activates.  

The following options are selectable: 

No reaction 

Switch on 

Switch of 

This output state can still be changed by the priority object. 

Behavior at end 

This parameter defines, which state the output should set, if the 
lock deactivates.  

The following options are selectable: 

No reaction 

Switch on 

Switch off 

State before lock 

State without lock 

State before lock: 
This restores the original state before the lock was activated. 
Switching telegrams received during the lock are ignored. 

State without lock: 
Here the state of the last received switching telegram is restored. 
This takes into account the received switching telegrams during 
the lock. Thus, when the lock is deactivated, the last received 
switching telegram is set.

 

 
Function (Universal output) 

If the universal output is selected on the parameter page "Actua-
tor 1: General", the actuator can be used as a switching output. 
A parameter for the scene function is also displayed. 

Group Object 

Type KNX 

Size 

Direction 

GO 11 Actuator 1: Output - Switch 

1.001 

1 Bit

From KNX 

 

Scene function 

With this parameter the scene function can be enabled or disa-
bled. If this functionality is enabled, the respective group object 
as well as the parameter page "Actuator 1: Scene function" are 
displayed for further configuration of scenes 1-16. 

Group Object 

Type KNX 

Size 

Direction 

GO 12 Actuator 1: Scene 

– Activ./Lrn. 

18.001 

1 Bit 

From KNX 

 
 
 
 
 
 
 
 
 
 

Содержание KNX IO 511

Страница 1: ...and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is successful ly powered by the KNX bus By pressing button A long the manual operation mode will be entered for channel A This is indicated by cyclic single flashing of LED Ch M in orange The actuator channel A can be switched on with button On and switched off with button Off The manual op...

Страница 2: ... settings It is possible to reset the device to its factory settings Disconnect the KNX Bus connector from device Press the KNX programming button and keep it pressed down Reconnect the KNX Bus connector of device Keep the KNX programming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 4 Wiring sch...

Страница 3: ... expiry of the time limit or manually the last state of the outputs remains until a new switching telegram is received again The following options are selectable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit Heartbeat Cyclic sending of values to the KNX Bus to indicate that the device is operational For the Cycle tim...

Страница 4: ...r to prevent unmeant switching Nevertheless the individual lamps can controlled by use of the priority object without cancel ing the lock F Lock function Polarity of object This parameter defines if the lock should be activated by receiv ing a 1 or by receiving a 0 The following options are selectable Lock active on 1 Lock active on 0 Behavior on start This parameter configures which state the out...

Страница 5: ...e The duration of the switch off delay is configured in this parame ter Input 1 0 Output 1 T 0 Retriggerable If these parameters are activated the respective delay time is restarted upon receipt of the corresponding switching signal Function Staircase function If the staircase function is selected on the parameter page Ac tuator 1 General a group object for the staircase function appears in additi...

Страница 6: ...control value is expressed in percent and defines the period during which the output is switched on in one cycle Example Cyclic time 10 Min Maximum control value PWM 80 Maximal output state ON 8 min OFF 2 min Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enab...

Страница 7: ... the lock is activated this value can be set with this parameter L Input B1 General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group objects are named Input with the channel number which ...

Страница 8: ...telegram can be configured here which is sent when the lock is deactivated O Function Impulse counter If the impulse counter function is selected further parameters are displayed in the general settings of the input channel Here the general settings of the impulse counter are made a scaled counter and or counter of the rate of change must also be se lected Input signal Here it can be selected whet...

Страница 9: ...it To KNX Shutter function The Shutter function parameter determines whether only one shutter direction or 1 button control is to be used Up Step Stop Down Step Stop Toggle direction User control The parameter User control determines the sending of tele grams on short and long button press Long Drive Short Step Stop Long button press Drive command via object 21 Short button press Stop step command...

Страница 10: ... button press the configured delay time is started Starting with the first scene position the next scene position of the list is sent with each short button press after the last scene position has been sent the list starts again from the beginning After the delay time has expired the list starts again at the first scene position on the next short button press When the lock function is used the sce...

Страница 11: ...t and continue Counter value is reset to 0 and continues in creasing on ever pulse Counter stop Counter value stays on limit value and must be reset by object Send on device restart It can be determined with this parameter whether the counter value should be sent when the device is restarted Reset via object If this function is activated the following object appears Group Object Type KNX Size Dire...

Страница 12: ...ameter is displayed to select the min imal delta from the last sent value for sending a new counter value Cyclically An additional parameter is displayed to configure the sending frequency of the counter variable On change and cyclically Both sending conditions are active Monitoring limit value When limit monitoring is activated the following object is dis played Group Object Type KNX Size Directi...

Страница 13: ... as the input of the next function Y Function 1 16 Timer Function name 10 Characters The function name can be chosen freely The name is visible in the group object entry in the ETS soft ware This makes it easier to work with the associated group objects because the given name is displayed there as a label Timer type Switch on delay A timer that switches ON after duration defined in Delay time s pa...

Страница 14: ... type AND gate The output is triggered on 1 if both inputs are switched on 1 Gate type OR gate The output is triggered on 1 if one or both inputs are switched on 1 Gate type XOR gate The output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are...

Страница 15: ...idered The device is a permanently connected equipment A readily accessible disconnect device shall be in corporated external to the equipment The installation requires a 16 A fuse for external overcurrent protection The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 511 ets4 Datasheet www weinzierl de en products 511 datasheet CE Declaration www ...