Weinzierl KNX IO 511 Скачать руководство пользователя страница 9

©

2019 WEINZIERL ENGINEERING GmbH 

Page 9/15

 

Function of (…) on press / short press 
Function of (…) on release / long press 

It is selectable for each object, which telegram is sent on open-
ing/closing the contact or on short/long button press.  

No reaction 

Switch on 

Switch off 

Toggle  

Output b 

Here you can show/hide the parameters and the object for out-
put b. 

 

Q.  Input B1: Dimming 

 

On selection of function Dimming following objects are visible: 

Group Object 

Type KNX 

Size 

Direction 

GO 21 Input B1: Dimming on/off 

– Switch 

1.001 

1 Bit

To KNX 

GO  22  Input  B1:  Dimming  relative 

– 

Brighter/Darker 

3.007 

4 Bit

To KNX 

 

Dimming function 

The dimming function parameter determines whether only one 
switching / dimming direction or 1-button control is to be used: 

On / Dim brighter 

Off / Dim darker  

Toggle direction 

If the input detects a short button press, a switching telegram is 
sent via object 21. On long button press, a relative dimming is 
sent over the entire dimming range to object 22. When releasing 
after long button press, a dimming-stop telegram is sent via 
object 22. 

The time for detection of a long button press can be set in the 
general parameters and is valid for all channels. 

R. 

Input B1: Shutter 

 

 

On selection of Shutter function following objects are visible: 

Group Object 

Type KNX 

Size 

Direction 

GO 21 Input B1: Drive start 

– Up/Down 

1.008 

1 Bit

To KNX 

GO 22 Input B1: Drive stop 

– Step/Stop 

1.007 

1 Bit

To KNX 

 
Shutter function 

The “Shutter function” parameter determines whether only one 
shutter direction or 1-button control is to be used: 

Up / Step-Stop 

Down / Step-Stop 

Toggle direction 

User control 

The parameter 

“User control” determines the sending of tele-

grams on short and long button press:  

Long = Drive / Short = Step/Stop 

Long button press: Drive command via object 21.       
Short button press: Stop/step command via object 22 

Short = Drive / Short = Step/Stop 

Alternately drive command via object 21 und stop/step 
command via object 22 on short button press, long 
button press is not evaluated 

Pressed = Drive / Release = Stop 

On button press drive command via object 21, on re-
leasing the button stop/step command via object 22 

The time for detection of a long button press can be set in the 
general parameters and is valid for all channels. 

S. 

Input B1: Send value 

 

If function Send value is selected, the following telegrams can be 
sent at button press: 

1 byte - Percent value 

Group Object 

Type KNX 

Size 

Direction 

GO  21  Input  B1:  Send  percent  value  (1 
byte) 

– Set value 

5.001 

1 Byte

To KNX 

 

1 byte - Integer value 

Group Object 

Type KNX 

Size 

Direction 

GO  21  Input  B1:  Send  integer  value  (1 
byte) 

– Set value 

5.010 

1 Byte

To KNX 

 

2 byte - Integer value 

Group Object 

Type KNX 

Size 

Direction 

GO  21  Input  B1:  Send  integer  value  (2 
byte) 

– Set value 

7.001 

2 Byte

To KNX 

 

2 byte - Float value 

Group Object 

Type KNX 

Size 

Direction 

GO  21  Input  B1:  Send  float  value  (2 
byte) 

– Set value 

9.001 

2 Byte

To KNX 

 

3 byte - RGB value 

Group Object 

Type KNX 

Size 

Direction 

GO  21  Input  B1:  Send  RGB  color  value 
(3 byte) 

– Set value 

232.600 

3 Byte

To KNX 

Содержание KNX IO 511

Страница 1: ...and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is successful ly powered by the KNX bus By pressing button A long the manual operation mode will be entered for channel A This is indicated by cyclic single flashing of LED Ch M in orange The actuator channel A can be switched on with button On and switched off with button Off The manual op...

Страница 2: ... settings It is possible to reset the device to its factory settings Disconnect the KNX Bus connector from device Press the KNX programming button and keep it pressed down Reconnect the KNX Bus connector of device Keep the KNX programming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 4 Wiring sch...

Страница 3: ... expiry of the time limit or manually the last state of the outputs remains until a new switching telegram is received again The following options are selectable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit Heartbeat Cyclic sending of values to the KNX Bus to indicate that the device is operational For the Cycle tim...

Страница 4: ...r to prevent unmeant switching Nevertheless the individual lamps can controlled by use of the priority object without cancel ing the lock F Lock function Polarity of object This parameter defines if the lock should be activated by receiv ing a 1 or by receiving a 0 The following options are selectable Lock active on 1 Lock active on 0 Behavior on start This parameter configures which state the out...

Страница 5: ...e The duration of the switch off delay is configured in this parame ter Input 1 0 Output 1 T 0 Retriggerable If these parameters are activated the respective delay time is restarted upon receipt of the corresponding switching signal Function Staircase function If the staircase function is selected on the parameter page Ac tuator 1 General a group object for the staircase function appears in additi...

Страница 6: ...control value is expressed in percent and defines the period during which the output is switched on in one cycle Example Cyclic time 10 Min Maximum control value PWM 80 Maximal output state ON 8 min OFF 2 min Stuck protection With the stuck protection it is intended to prevent the valve from being damaged by corrosion or calcification that it can no longer be moved In case stuck protection is enab...

Страница 7: ... the lock is activated this value can be set with this parameter L Input B1 General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group objects are named Input with the channel number which ...

Страница 8: ...telegram can be configured here which is sent when the lock is deactivated O Function Impulse counter If the impulse counter function is selected further parameters are displayed in the general settings of the input channel Here the general settings of the impulse counter are made a scaled counter and or counter of the rate of change must also be se lected Input signal Here it can be selected whet...

Страница 9: ...it To KNX Shutter function The Shutter function parameter determines whether only one shutter direction or 1 button control is to be used Up Step Stop Down Step Stop Toggle direction User control The parameter User control determines the sending of tele grams on short and long button press Long Drive Short Step Stop Long button press Drive command via object 21 Short button press Stop step command...

Страница 10: ... button press the configured delay time is started Starting with the first scene position the next scene position of the list is sent with each short button press after the last scene position has been sent the list starts again from the beginning After the delay time has expired the list starts again at the first scene position on the next short button press When the lock function is used the sce...

Страница 11: ...t and continue Counter value is reset to 0 and continues in creasing on ever pulse Counter stop Counter value stays on limit value and must be reset by object Send on device restart It can be determined with this parameter whether the counter value should be sent when the device is restarted Reset via object If this function is activated the following object appears Group Object Type KNX Size Dire...

Страница 12: ...ameter is displayed to select the min imal delta from the last sent value for sending a new counter value Cyclically An additional parameter is displayed to configure the sending frequency of the counter variable On change and cyclically Both sending conditions are active Monitoring limit value When limit monitoring is activated the following object is dis played Group Object Type KNX Size Directi...

Страница 13: ... as the input of the next function Y Function 1 16 Timer Function name 10 Characters The function name can be chosen freely The name is visible in the group object entry in the ETS soft ware This makes it easier to work with the associated group objects because the given name is displayed there as a label Timer type Switch on delay A timer that switches ON after duration defined in Delay time s pa...

Страница 14: ... type AND gate The output is triggered on 1 if both inputs are switched on 1 Gate type OR gate The output is triggered on 1 if one or both inputs are switched on 1 Gate type XOR gate The output is triggered on 1 if the two inputs are not equal Gate type NAND gate The output is triggered on 1 if one or both inputs are switched off 0 Gate type NOR gate The output is triggered on 1 if both inputs are...

Страница 15: ...idered The device is a permanently connected equipment A readily accessible disconnect device shall be in corporated external to the equipment The installation requires a 16 A fuse for external overcurrent protection The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 511 ets4 Datasheet www weinzierl de en products 511 datasheet CE Declaration www ...

Отзывы: