Installation and Startup Guide
This document covers the installation of MT8073iE Series HMI, for the detailed specifications and
operation, please refer to Brochure and EasyBuilder Pro User Manual.
Install Environment:
NEMA Rating
The
HMI product is NEMA 4 rated (Indoor Only).
Electrical
Environment
The
HMI product has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2)
The HMI product is certified in accordance with ATEX zone 2/22 categories
3 G/D. The unit has to be installed in an additional enclosure ensuring a
minimal protection level for 3G/D equipment. The enclosure equipped with
the unit has to be certified and shouldn’t be opened when an explosive
atmosphere is present.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4)
This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5)
Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
Unpacking the Unit
Unpack and check the delivery. If damage is found,
notify the supplier.
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws. Screw Torque: 2.6 ~ 3.9 lbf.in. (For reaching waterproof effect and preventing the panel
from being deformed.)
Type
A(mm)
B(mm)
MT8073iE
192
138
USB Stick Clamp Usage
Combining the USB Stick with the clamp and the tying strap can prevent USB stick from disconnecting
with HMI when strong vibration is present.
1. Insert the USB connector to the clamp and tie them together with the tying strap.
2. Press the spring and insert the USB stick into HMI.
Power Connections
System Settings
When HMI is powered up and displays image, press the
system setting button in the lower-right corner of the screen.
(Default System Password: 111111)
Go to the Network tab, you may choose to auto get DHCP IP, or
designate your own IP.
MT8073iE has two10/100/1000 Base-T Ethernet ports.
The default IP addresses are:
LAN 1: DHCP
LAN 2: 192.168.100.1
MT8073iE series
Installation Instruction
1
2
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
NOTE:
1. Conne
ct positive DC line to the ‘+’ terminal and the DC
ground to the ‘-’ terminal.
2. When using a USB cable to download project file, please
do not connect HMI with PLC and PC simultaneously to
prevent potential difference from destroying USB ports of
HMI and PC.
(A)
(B)
Cutout
3
5
4
(1)
(2)
(3)
(5) (4)
(6)
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
(5) USB Stick Clamp & Tying Strap *1
(6) Fuse 1.25A/250V 5*20mm *1