iR-COP
32
4005h
01h
Number of digital outputs of the 1
st
module. UNSIGNED16
ro
02h
Number of digital outputs of the 2
nd
module.
UNSIGNED16
ro
……
……
……
……
10h
Number of digital outputs of the 16
th
module.
UNSIGNED16
ro
4006h
01h
Number of analog input channels of the 1
st
module.
UNSIGNED16
ro
02h
Number of analog input channels of the 2
nd
module.
UNSIGNED16
ro
……
……
……
……
10h
Number of analog input channels of the 16
th
module.
UNSIGNED16
ro
4007h
01h
Number of analog output channels of the 1
st
module.
UNSIGNED16
ro
02h
Number of analog output channels of the
2
nd
module.
UNSIGNED16
ro
……
……
……
……
10h
Number of analog output channels of the
16
th
module.
UNSIGNED16
ro
7
Power Consumption
I/O modules use system power supply and external drive power supply, and these
two types of power supply should be calculated separately. Operating coupler and
module requires system power supply while switching I/O and driver requires
external power supply. When calculating power consumption for coupler, the power
needed for the connected modules should be put into the equation. Please consider
power requirements while connecting multiple modules. The following tables show
references on power consumption of couplers and modules.
Type
Device
Consumption(5V)
Power Supply(5V)
Coupler
iR-ETN
220mA/1.1w
2A/10w
iR-COP
170mA/0.85w
2A/10w
Digital I/O
iR-DM16-P
130mA/0.65w
--
iR-DM16-N
130mA/0.65w
--
iR-DQ08-R
220mA/1.1w
--
iR-DQ16-N
205mA/1.02w
iR-DQ16-P
196mA/0.984w
iR-DI16-K
83mA/0.418w