The default values shall be set valid after the CANopen device is reset (NMT service
reset node for sub-index from 01h to 7Fh, NMT service reset communication for
sub-index 02h) or power cycled.
Communication Parameters (1000h~1FFFh):
Index
Sub-index Description
Type
Default
100Ch
00h
Guard time
UNSIGNED16
0
100Dh
00h
Life time factor
UNSIGNED8
0
1014h
00h
EMCY COB-ID
UNSIGNED32
80h + Node-ID
1015h
00h
EMCY inhibit time
UNSIGNED16
0
1016h
01h
Consumer heartbeat time
UNSIGNED32
0
1017h
00h
Producer heartbeat time
UNSIGNED16
0
1029h
01h
Communication error
UNSIGNED8
0
1400h
01h
COB-ID used by
RPDO1
UNSIGNED32
200h + Node-ID
02h
Transmission type of RPDO1
UNSIGNED8
FFh
1401h
01h
COB-ID used by
RPDO2
UNSIGNED32
300h + Node-ID
02h
Transmission type of RPDO2
UNSIGNED8
FFh
1402h
01h
COB-ID used by
RPDO3
UNSIGNED32
400h + Node-ID
02h
Transmission type of
RPDO3
UNSIGNED8
FFh
1403h
01h
COB-ID used by
RPDO4
UNSIGNED32
500h + Node-ID
02h
Transmission type of RPDO4
UNSIGNED8
FFh
1404-
01h
COB-ID used by
RPDO5-8
UNSIGNED32
8000000