iR-AQ04-VI iR-AM06-VI iR-AI04-VI
16
can be cleared by giving a command (restart recording).
Setting
Description
Default
Input Max./Min. Value
Allowable range: -32768~32767
0
Error Code
Error Code
Description
0
Power error
1
Hardware error
2
Device isn't calibrated
3
Reserved
4
Conversion cannot be performed.
5-7
Reserved
8
Input Channel 0 error
9
Input Channel 1 error
10
Input Channel 2 error
11
Input Channel 3 error
12
Output Channel 0 error
13
Output Channel 1 error
14
Output Channel 2 error
15
Output Channel 3 error
Command
Value
Description
0x0001
Restore factory default
0x0002
Reset the max./min. value of analog output channel 0
0x0003
Reset the max./min. value of analog output channel 1
0x0004
Reset the max./min. value of analog output channel 2
0x0005
Reset the max./min. value of analog output channel 3
0x0006
Reset the max./min. value of analog output channel 0-3
Channel Detection
Bit
Description
Value
1
0
0
Analog Input Channel 0 Detection
Enable
Disable
1
Analog Input Channel 1 Detection
Enable
Disable
2
Analog Input Channel 2 Detection
Enable
Disable
3
Analog Input Channel 3 Detection
Enable
Disable
Содержание iR-AI04-VI
Страница 7: ...iR AQ04 VI iR AM06 VI iR AI04 VI 5 5 Wiring...
Страница 8: ...iR AQ04 VI iR AM06 VI iR AI04 VI 6 2 3 and 4 wire Analog Sensor connection at inputs 2 wire...
Страница 9: ...iR AQ04 VI iR AM06 VI iR AI04 VI 7 3 wire...
Страница 10: ...iR AQ04 VI iR AM06 VI iR AI04 VI 8 4 wire AG connected to V contact with low resistance...