iR-AQ04-VI iR-AM06-VI iR-AI04-VI
13
channel 1 is opened, only channel 1 can perform conversion while the rest cannot.
Analog Input – Filter
6.6
The built-in filter enhances signal precision to achieve better control. Setting a slower
conversion rate will get a better signal quality. By default the conversion time is 2ms.
Setting 50ms can effectively filter out noises in a 50/60Hz environment.
The filter can stabilize the signal by averaging sampled values, in order to achieve
better control.
7.
Registers
Address
Description
Default
Read/Write
0
Analog
Output
Channel 0 Output Mode
1
Read/Write
1
Channel 1 Output Mode
1
Read/Write
2
Channel 2 Output Mode
1
Read/Write
3
Channel 3 Output Mode
1
Read/Write
4
Channel 0 Scale Range Upper Limit
32000
Read/Write
5
Channel 1 Scale Range Upper Limit
32000
Read/Write
6
Channel 2 Scale Range Upper Limit
32000
Read/Write
7
Channel 3 Scale Range Upper Limit
32000
Read/Write
8
Channel 0 Scale Range Lower Limit
-32000
Read/Write
9
Channel 1 Scale Range Lower Limit
-32000
Read/Write
10
Channel 2 Scale Range Lower Limit
-32000
Read/Write
11
Channel 3 Scale Range Lower Limit
-32000
Read/Write
12
Channel 0 Update Time
0
Read/Write
13
Channel 1 Update Time
0
Read/Write
14
Channel 2 Update Time
0
Read/Write
15
Channel 3 Update Time
0
Read/Write
16
Error Code
0
Read
17
Command
0
Read/Write
18
Channel Detection
FFh
Read/Write
19
Analog
Input
Conversion Time
0
Read/Write
20
Channel 0 Input Mode
1
Read/Write
21
Channel 1 Input Mode
1
Read/Write
22
Channel 2 Input t Mode
1
Read/Write
23
Channel 3 Input Mode
1
Read/Write
24
Channel 0 Scale Range Upper Limit
32000
Read/Write