background image

3

 

 

Caution 

Supply Voltage 

Condition 

Do not power the MT-600 and inductive DC loads, or input circuitry to the 

controller, with the same power supply. Note: The 24 VDC output from 

some controllers may not have enough current to power the MT-600. 

 

Caution  

Wire Routing 

Wire lengths should be minimized (Maximum 1600’ (500 m) shielded, 

1000’ (300 m) unshielded). 
Wires should be run in pairs with a neutral or common paired with a hot or 

signal line. 
If wiring is to be exposed to lightning or surges, use appropriate surge 

suppression devices. 
Keep AC, high energy, and rapidly switching DC wiring separate from 

signal wires. 
Equip ungrounded DC supplies with a resistor and capacitor in parallel to 

earth ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1MOhm and 4700pF. 

 

Connection 

To make a connection, strip about 3/8” of insulation off the end of the wire, 

turn the connector screw counterclockwise until the gap is wide open, insert 

the wire all the way in, and turn the screw clockwise until it’s tight. 
Connect positive DC line to the ‘+24V’ terminal and the DC ground to the 

‘0V‘ terminal. 

2.2.2 Grounding Requirements 

 

 

Chassis ground must be used.    DC ground is not directly coupled to Earth 

ground internally. It is preferable not to ground DC negative return to chassis 

ground as poor site earths can introduce noise into a system, but if necessary 

an earth connection should be made, from the power supply return point to 

the central star earth point. Ground conductors should be as short and as large 

in size as possible. The conductors must always be large enough to carry the 

maximum short circuit current of the path being considered. Ground 

conductors should be connected to a tree from a central star earth ground 

point. This ensures that no ground conductor carries current from any other 

branch. 

 

 

 

2.2.3 CE Requirements 

To make an MT-600 comply with EMC directives, and to reduce susceptibility to electrical 

interference, a separate #14 AWG ground wire should be taken to the chassis ground terminal of the 

power connector. This ground connection should be run directly to the central star earth connection 

point (as recommended in most Installation Instructions). 

 

2.2.4 Safety Guidelines 

This section presents recommended installation practices, and procedures. Since no two 

applications are identical, these recommendations should be considered as guidelines. 

 

Hardware 
Considerations 

WARNING! 
The system designer should be aware that devices in Controller systems could 

fail and thereby create an unsafe condition. Furthermore, electrical 

interference in an operator interface, such as an MT-600, can lead to 

equipment start-up, which could result in property damage and/or physical 

injury to the equipment operator. 
If you, or your company, use any programmable control systems that require 

an operator or attendant, you should be aware that this potential safety hazard 

exists and take appropriate precautions. Although the specific design steps 

depend on your particular application, the following precautions generally 

apply to installation of solid-state programmable control devices. In addition, 

these precautions conform to the guidelines for installation of Controllers as 

recommended in the NEMA ICS 3-304 Control Standards. 

Programming 

To conform with ICS Safety Recommendations, checks should be placed 

Содержание EasyView MT-600 Series

Страница 1: ...en tested to conform to European CE requirements This means that the circuitry is designed to resist the effects of electrical noise This does not guarantee noise immunity in severe cases Proper wire...

Страница 2: ...le gases vapors or dusts z The unit should not be installed where fast temperature variations and or high humidity are present This will cause condensation of water in the device z Do not install thes...

Страница 3: ...st always be large enough to carry the maximum short circuit current of the path being considered Ground conductors should be connected to a tree from a central star earth ground point This ensures th...

Страница 4: ...ht be introduced if programs are changed while the equipment is in operation z The ICS 3 304 81 Safety Recommendations are reproduced by permission of the National Electrical Manufacturers Association...

Страница 5: ...5 Pin assignment of the 9 Pin Female SUB D COM3 RS 485 Port Pin Symbol RS 485 4wire RS 485 2wire 1 2 Tx Transmitted Data Data 3 Tx Transmitted Data Data 4 Rx Received Data 5 Rx Received Data 6 GND Sig...

Страница 6: ...EC electromagnetic emissions and immunity z Machinery Directive 89 392 EEC 91 368 EEC 93 44 EEC 93 68 EEC machine safety z MT500 products will be CE marked to indicate compliance with the EMC Directiv...

Страница 7: ...Hz DRAM 64MB Storage 32MB Flash memory on board 1 CompactFlash card slot RTC Yes General Specification Input Power 21 25 VDC Power Consumption 350 mA 24VDC CE Complies with EN50081 2 and EN50082 2 sta...

Страница 8: ...B client b Sound ports h USB Master c MIC ports i Com1 RS232 d Ethernet port RJ 45 j Com2 RS232 e Fuse k Com3 RS485 f Power connector Front View Side View Cutout dimensions MT 608S 222mm 8 74 W x 167m...

Отзывы: