WATER
BOILER
—
Boiler Manual
Connect water piping
(continued)
&IGURE
Multiple zoning with zone valves –
Temperatures below 140 °F
&IGURE
Multiple zoning with circulators –
Temperatures below 140 °F
1. If system water temperature requirements are less
than 140 °F, such as radiant panels or converted
gravity systems, use piping as shown in Figure 10
or 11.
2. If system piping is plastic without an oxygen barrier,
a heat exchanger must be used.
3. Follow instructions on page 14 and 15 to install
near-boiler piping.
4. Zoning with circulators (Figure 10)
A 3IZE EACH CIRCULATOR TO INDIVIDUAL CIRCUIT REQUIRE
-
ments.
b. Remove circulator (when furnished as standard equip-
ment).
c. Install balancing valves to adjust flow to distribute heat
TOALLZONES
D 3EPARATERELAYISREQUIREDFOREACHCIRCULATOR
:ONINGWITHZONEVALVES&IGURE
a. Install balancing valves to adjust flow to distribute heat
TOALLZONES
B 3EPARATETRANSFORMERISREQUIREDTOPOWERZONEVALVES
2EFERTOh7EIL-C,AIN:ONE6ALVE7IRING
Guide” for details.
6. To set the valves,
A
and
B
:
A 3ETTHEVALVESWHILETHESYSTEMISCOOLSETTINGFORTHE
coldest expected water temperature (usually 60 °F
since the system will often drop to room temperature
between cycles).
B 3TARTWITHVALVE
A
fully closed and
B
fully open.
c. Gradually open valve
A
while closing
B
until the
temperature at gauge
reads 130 °F when gauge
A
reads 60 °F.
D .OTETHATVALVE
A
regulates the amount of hot water
from the boiler supply, which mixes with return water.
Valve
B
regulates the amount of system water flowing
through the boiler secondary loop.
Piping MULTIPLE ZONES — System temperature below 140 °F
Zone 1
Zone 2
1
1
1
1
2
2
3
4b
4a
6
6
7b
7a
8
Max.
12”
UO016
3
1 Isolation
valve
2
Flow control valve
3 Circulator
4
System temperature gauges
5 Zone
valve
6 Drain
valve
7
System temperature valves. Adjust valves
8
Blend temperature gauge
9
Boiler temperature gauge (not shown)
Part number 550-141-986/0112
17
Содержание Ultra Oil
Страница 3: ...WATER BOILER Boiler Manual THE WATER BOILER Part number 550 141 986 0112 3...
Страница 35: ...WATER BOILER Boiler Manual Replacement parts continued Burner door parts Part number 550 141 986 0112 35...
Страница 37: ...WATER BOILER Boiler Manual Replacement parts continued Jacket and control parts Part number 550 141 986 0112 37...
Страница 40: ...40 WATER BOILER Boiler Manual 40...