WATER

 

BOILER

 — 

Boiler Manual

Clean boiler flueways and check 
refractory linings

 

Make sure all electrical connections to boiler 
are turned off and wait until boiler is warm, 
not hot, before cleaning. Failure to do so 
will result in severe personal injury, death or 
substantial property damage.

  The boiler contains fiberglass and ceramic 

lBERMATERIALS5SECAREWHENHANDLINGTHESE

materials, per instructions on page 26 of this 
manual. Failure to comply could result in 
severe personal injury.

1.  Remove jacket front panel and burner cover.

 3HUTOFFOILVALVES!RRANGEDRIPPANSUNDERTHEAREAS

of oil piping that will be disconnected.

3.  Disconnect the oil line at the burner. Provide means to 

prevent oil from dripping.

4.  Disconnect burner 120-volt harness  at the jacket cross-

tie (located beneath the burner door).

 

Failure to disconnect the burner wiring har-
nesses before opening the burner door can 
cause damage to the burner and boiler wiring.

 3WINGTHEBURNERDOOROPENCOMPLETELY3EE&IGURE

6.  Line the combustion chamber floor with newspaper 

to catch any soot that will be loosened in the cleaning 
process.

 -ODEL5/'0(lRINGRATEONLYˆ2EMOVETHE

two flue baffles.

 3TARTINGATTHETOPOFTHEBOILERUSEAWIREmUEBRUSH

to thoroughly clean all fins.

 /NCE THE mUEWAYS ARE CLEANED CAREFULLY REMOVE THE

paper from the floor of the combustion chamber.

10.  Verify burner door sealing rope is intact.
11. Visually check condition and position of the refracto-

ries in the burner mounting door. Replace any parts as 
necessary.

-ODEL5/'0(lRINGRATEONLYˆ2EPLACETHE

two flue baffles.

13.  Close burner mounting door. Insert and tighten burner 

door bolts securely.

 

Maintain a gas-tight seal to avoid possible flue 
gas leakage and carbon monoxide emissions, 
which can lead to severe personal injury or 
death.

14.  Check the breeching for sooting and clean if necessary. 

&IGURE

Access to boiler flueways

Annual service and start-up

 

(continued)

15.  Replace the jacket front panel and breeching.
16.  Reconnect the oil line and all electrical connections.

Perform boiler start-up

1.  Follow instructions in this manual and the burner 

manual to start-up and adjust burner and boiler.

2.  Verify operation of all controls, including all limit 

devices and combustion controls.

Review with owner

2EVIEWTHE5SERS)NFORMATION-ANUALWITHTHEOWNER

or boiler operator.

Record the service call

Record the service call on the form on page 25.

UO040

Burner wiring harness

Part number 550-141-986/0112

29

Содержание Ultra Oil

Страница 1: ...tructions includ ing this manual and all other information shipped with the boiler before installing Perform steps in the order given Failure to comply could result in severe personal injury death or...

Страница 2: ...ass During normal operation the sight glass is located at the 12 00 position To view the burner ame loosen the center mounting bolt and rotate so the sight glass is in the 6 00 position 17 Over re pre...

Страница 3: ...WATER BOILER Boiler Manual THE WATER BOILER Part number 550 141 986 0112 3...

Страница 4: ...ave the boiler model number from the boiler rating label and the CP number from the boiler jacket You may list the CP number in the space provided on the Installation Certi cate found on page 24 Consi...

Страница 5: ...Theboilerheatexchanger can be damaged by build up or corrosion due to sedi ment s O NOT USE PETROLEUM BASED CLEANING OR SEALING compounds in boiler system Gaskets and seals in the system may be damage...

Страница 6: ...i ed service technician Beginning of heating season Call a qualified service technician to perform annual service Every day during heating season Keep area free of combustible materials Check that boi...

Страница 7: ...3 2 1 3 3 1 4 43 3 8 241 3 5 3 6 1 5 4 1 2 2 6 4 2 8 4 2 1 5 3 1 3 1 3 5 3 8 31 1 1 3 5 3 42 3 31 2 1 3 3 3 1 7 3 3 3 5 3 23 1 43 3 3 432 6 2 2 3 31 2 2314 3 4 8 241 3 5 3 6 1 5 4 1 2 2 6 4 723 6 3 1...

Страница 8: ...r jacket surfaces s 4OP OF ONTROL 0OD COVER INCHES s 3IDES AND BACK INCHES 5 Burner cover s LL DIRECTIONS INCHES Combustible clearances always take pre cedence over service clearances For service acce...

Страница 9: ...and replace Air from outside the building When outside air is used connect each opening directly or by ducts to the outdoors or to crawl or at TIC SPACE THAT FREELY CONNECTS WITH OUTDOORS 3IZE PER be...

Страница 10: ...B 3LIDE THE OTHER CHANNEL UNDER THE OTHER BOILER LEG 0LACE THE channel directly over the crate base runner as shown 5 Figure 3 With the boiler resting securely on the two shipping chan NELS SCREW A LE...

Страница 11: ...posite side Place the hinge bracket on that side and tighten the two screws to secure the bracket Also tighten the two screws on the other side 7 Carefully lift the burner door and position so the doo...

Страница 12: ...n in chimney 4ABLE Chimney venting vent sizing Model Minimum breeching diameter inches Minimum I B R chimney size inches Minimum chimney height feet Rect Round UO 3 5 8 x 8 6 x 6 liner 6 15 UO 4 6 UO...

Страница 13: ...n burner and boiler are properly installed breeching draft will be approximately 0 01 to 0 02 W C Install barometric control in breech ing per control manufacturer s instructions when excess draft nee...

Страница 14: ...LSO REFER TO TAG ATTACHED TO RELIEF VALVE FOR MANU facturer s instructions 2ELIEF VALVE DISCHARGE PIPING To avoid water damage or scalding due to relief valve operation s ISCHARGE LINE MUST BE CONNEC...

Страница 15: ...valve and makeup water added through ll valve Eventual section failure can result CLOSED expansion tank Figure 7 s NSURE EXPANSION TANK SIZE WILL HANDLE BOILER AND system water volume and temperature...

Страница 16: ...TO ALL ZONES IGURE Multiple zoning with circulators Temperatures 140 F and higher IGURE Multiple zoning with zone valves Temperatures 140 F and higher D 3EPARATE RELAY IS REQUIRED FOR EACH CIRCULATOR...

Страница 17: ...ribute heat TO ALL ZONES B 3EPARATE TRANSFORMER IS REQUIRED TO POWER ZONE VALVES 2EFER TO h7EIL C AIN ONE 6ALVE 7IRING Guide for details 6 To set the valves A and B A 3ET THE VALVES WHILE THE SYSTEM I...

Страница 18: ...l state or local codes s ANADA 3 ANADIAN LECTRICAL ODE 0ART AND ANY LOCAL codes Electrical knockouts Terminal strip Control Pod cover UO018 Remove cover for unrestricted access to wiring compartment C...

Страница 19: ...THE BOILER TERMINAL STRIP AS SHOWN ON the boiler wiring diagram Provide hot neutral and ground wires routed in metal conduit Thermostat wiring s Install thermostat on inside wall away from in uences o...

Страница 20: ...ALERT G BLOCKED VENT SHUTOFF SWITCH CANADA ONLY LOW WATER CUT OFF H N G N H JUMPER NOTE 5 LIMIT SENSOR NOTE 8 BK BURNER DISCONNECTS Wiring Diagram NOTES 1 All wiring must be installed in accordance wi...

Страница 21: ...urner Wiring Carlin 60200 Riello F5 Burner Wiring FIELD WIRING FACTORY WIRED SUB BASE W R B G BLACK WHITE RED GREEN GROUND BLACK BROWN Oil Valve 11 BLACK WHITE BROWN M Capacitor BLUE BLUE Electric Air...

Страница 22: ...e used to prevent ow of oil in case of oil line break s 3UPPORT OIL LINES AS REQUIRED BY CODES s AKE TANK CONNECTIONS WITH SWING JOINTS OR COPPER tubing to prevent breaking in case the tank settles Ma...

Страница 23: ...perty damage 6ENT AIR FROM SYSTEM 2EPEAT STEPS AND UNDER h ILL THE SYSTEM v IR in system can interfere with water circulation and cause improper heat distribution HECK BOILER AND SYSTEM PIPING FOR LEA...

Страница 24: ...ing if available set PROPERLY 2EFER TO h4HERMOSTAT WIRINGv PAGE 12 Boiler cycled with thermostat Raise to highest setting and verify boiler goes through normal start up cycle Lower to lowest setting a...

Страница 25: ...s filled with water 9 Start unit and verify combustion settings with combustion test equipment 10 Verify operation of all controls on boiler See boiler manual and burner manual for procedures The boil...

Страница 26: ...onditions Current 3 RECOMMENDATIONS CAN BE FOUND ON THE 3 WEB SITE AT HTTP WWW CDC GOV NIOSH HOMEPAGE HTML 3 APPROVED RES pirators manufacturers and phone numbers are also listed on this web site s 7E...

Страница 27: ...re increase or contracts as the water cools Tanks may be open closed or diaphragm or bladder type Follow guidelines in this manual for the best location of the expansion tank PEN TYPE located above hi...

Страница 28: ...ld result in unsafe pressure buildup which can result in severe personal injury death or substantial property damage Following installation the valve lever must be operated AT LEAST ONCE EACH YEAR to...

Страница 29: ...ATE ONLY 2EMOVE THE two ue baf es 3TARTING AT THE TOP OF THE BOILER USE A WIRE mUE BRUSH to thoroughly clean all ns NCE THE mUEWAYS ARE CLEANED CAREFULLY REMOVE THE paper from the oor of the combustio...

Страница 30: ...ING HARNESS AT THE JACKET crosstie located beneath the burner door Failure to disconnect the burner wiring har ness before opening the burner door can cause damage to the burner and boiler wiring s 4U...

Страница 31: ...e the electrical tray in position 15 Remove the jacket side panels by pulling back edge away from the back of the boiler and then disengag ing the keyholes from the jacket front screws 16 Remove the e...

Страница 32: ...1 928 221 6 Washers 4 required 562 248 668 7 P T gauge temperature sensor well 592 300 025 8 Limit control sensor well 592 300 026 9 Mounting clip for P T gauge and limit well 512 400 001 10 P T gauge...

Страница 33: ...WATER BOILER Boiler Manual Replacement parts continued Boiler section assembly parts Part number 550 141 986 0112 33...

Страница 34: ...X Purchase locally 2 Burner door 330 054 308 3 Burner door hinge bracket 466 900 000 4 K R Q V Purchase locally 5 Y Y Y A A 386 902 000 6 Observation port gasket requires water glass adhesive 590 318...

Страница 35: ...WATER BOILER Boiler Manual Replacement parts continued Burner door parts Part number 550 141 986 0112 35...

Страница 36: ...anel UO 3 UO 4 UO 5 426 900 005 426 900 006 426 900 007 6 Jacket rear panel if required order insulation below 426 900 001 7 Jacket rear panel insulation 591 222 181 8 Jacket cross tie 426 900 008 9 B...

Страница 37: ...WATER BOILER Boiler Manual Replacement parts continued Jacket and control parts Part number 550 141 986 0112 37...

Страница 38: ...1 Boiler circulator is shipped loose Circulator may be mounted on either boiler supply or return piping 2 Relief valve is shipped loose supplied with elbow and nipple to install in rear section tappin...

Страница 39: ...An additional allowance should be made for unusual piping and pick UP LOADS ONSULT LOCAL 7EIL C AIN 3ALES FlCE 3EE PAGE FOR MINIMUM BREECHING AND CHIMNEY SIZING OILER DRAFT LOSSES ARE BASED ON OPERAT...

Страница 40: ...40 WATER BOILER Boiler Manual 40...

Отзывы: