ADVANCED SETUP –
CIRCULATOR EXERCISING
For each circulator, select whether you want the U-Control to
1.
automatically start the circulator and run for 10 seconds for each
72-hour period of inactivity.
Figure 101
U-Control system types and preset parameters
System type
Display
Preset temperatures
Note
8-character
3-char
Max Target
Temp
Outdoor Temp
for Max Target
Min Target
Temp
Outdoor Temp
for Min Target
Fan-coil
FAN-COIL
FCL
190
0
140
70
Finned tube baseboard
FIN BASE
FTB
180
0
130
70
Cast iron baseboard
IRN BASE
CIB
180
0
120
70
Cast iron radiators
RADIATOR
CIR
180
0
120
70
Radiant – slab on grade
RAD SLAB
RSG
120
0
80
70
Radiant – thin slab
RAD SLAB
RTS
140
0
80
70
Radiant – below floor
(staple up)
RADFLOOR
RSU
160
0
90
70
Radiant – above floor
(sleeper system)
RADFLOOR
RAF
140
0
90
70
Custom
CUSTOM
CUS
190
0
70
70
• Does not pass along Add’l Heat Demand
DHW – system
DOMESTIC
DHW
190
DHW heating ignores outdoor reset and
warm weather shutdown
• U-Control modulates to system tempera
-
ture sensors
DHW – direct
DOMESTIC
DHW
190
• U-Control modulates to boiler temperature
sensors
• Does not pass along Add’l Heat Demand
ADVANCED SETUP –
FREEZE PROTECTION CIRCULATORS
This function automatically fires the boiler at low fire
1.
and starts the circulators chosen if the heat exchanger
sensor detects a temperature less than 40 °F. The circula-
tors turn off when the temperature rises above 45 °F.
ADVANCED SETUP –
MAINTENANCE INFO
Use this section to enter contractor’s information and
1.
to enter an automatic notice for maintenance (default
is 12 months). Because this shows on the display, it is an
automatic means of notifying the homeowner of need
for scheduled maintenance by the technician. Update
the screen reminder to reset for the next maintenance
date.
U-Control operation and setup — advanced
(continued)