Part number 550-100-131/0120
– 92 –
®
gas
-
fired
water
boiler
— 220/299/300/399
Boiler Manual
Check-out/startup verification
Adjust and test boiler controls
1. Follow instructions in this manual to set and verify operation
of the boiler controls.
2. Follow low water cutoff manufacturers instructions (If in-
stalled).
Have the following been done?
❏
Control set for the correct boiler model?
❏
Installation date and installer contact information entered
into Control?
❏
Boiler and heat distribution units filled with water?
❏
Water chemistry verified per page 86?
❏
Sentinel X100 corrosion inhibitor added and water tested to
be within range?
❏
Automatic air vents, if used, opened one full turn?
❏
Air purged from system?
❏
Air purged from gas piping? Piping checked for leaks?
❏
Condensate line primed?
❏
Propane venturi installed for propane firing and propane
conversion label affixed to jacket?
Evergreen
®
boilers are shipped ready to fire natural
gas ONLY. To fire on propane, you must follow the
instructions in this manual to install the propane
venturi kit, See page 12. Failure to comply could
result in severe personal injury, death or substantial
property damage.
❏
Thermostat circuit wiring checked to ensure there are no
stray voltages?
❏
Followed Operating Instructions, Figure 87, page 89?
❏
Burner flame and combustion verified per pages 90 and 91?
❏
Control operation for space heating and DHW (if used) veri-
fied per this manual?
❏
Additional field-installed controls tested as outlined by control
manufacturers? (Boiler should be operating and should go off
when controls are tested. Verify controls cause automatic reset
lockout or manual reset lockout as desired.)
❏
Additional field-installed limit control(s) set to system tem-
perature requirements? Balancing valves and controls adjusted
to provide design temperature to system?
❏
Flow adjusted/balanced for each zone of multiple zones
systems?
❏
Thermostat heat anticipator (if available) set properly?
❏
Boiler cycled with thermostats (and with DHW aquastat, if
installed) — Raised to highest setting and verified boiler goes
through normal startup cycle? Lowered to lowest setting and
verified boiler goes off?
❏
Natural gas input measured? (page 90)
❏
Incoming gas pressure checked by connecting manometer to
gas valve ahead of boiler? (Gas pressure must be at least the
minimum values given on page 18, with boiler operating at
high fire, and no more than 14 inches (356 mm) w.c. with
boiler operating or boiler off.)
❏
Observed several operating cycles for proper operation?
❏
Room thermostats set to desired room temperature (and
DHW aquastat, if installed, to desired DHW storage tem-
perature)?
❏
All instructions shipped with this boiler reviewed with owner
or maintenance person?
Before leaving:
❏
Fill in
Installation certificate
, page 131.
❏
Return instructions to envelope and give to owner or place
inside boiler housing.
Fill out start-up data on the Installation
and Service Certificate, page 131.
Startup — final checks
(continued)
❏
Check Heat exchanger and vent seals
1. Operate the boiler on HIGH fire.
2. Using an inspection mirror, move the mirror around all heat
exchanger joints and vent pipe connections at the top of the
boiler and at the connection to the condensate dish.
3. A leak would appear as vapor on the surface of the mirror.
4. If there is any indication of a leak at any joint, immediately
shut down the boiler.
a. If possible, tighten the retaining screws or nuts (without
over-tightening).
b. If this does not correct the problem, disassemble the com-
ponents where the leak appeared. Use the procedures given
in the Maintenance section of this manual.
c. When disassembling components, inspect gaskets to see
if there is damage. Replace any damaged gasket.
d. Contact your Weil-McLain representative if the problem
cannot be addressed with the information provided in
this manual.
5. Condensate dish joint
a. If the inspection mirror check shows a leak at the con-
densate dish-to-heat exchanger joint.
or
If the mirror test does not reveal a leak at the condensate
dish joint, but there are signs of weepage or other indica-
tions that there might be leakage, the boiler must not be
operated until a new sealing ring is obtained. Follow the
instructions supplied with the sealing kit to disassemble
boiler components as necessary to access and replace
the seal.