1
Part Number 550-110-032/0607
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4
Checkout procedure
Room thermostat anticipator settings
Water without tankless heater — 0.40 amps
Water with tankless heater — 0.20 amps
Steam — Select based on gas valve and damper. See table below.
1. See pages 1-18 for “Lighting Instructions”.
. Raise room thermostat to call for heat. Damper actuator will slowly open damper.
. When damper is fully open, main gas valve will open and main burners will ignite.
Damper must be fully open before main burners light. If damper does not fully
open, flue products will escape into house, causing severe personal injury or
death.
. Lower thermostat setting. Main burner flames will go out, then damper will close.
. Repeat steps 1 through several times to verify operation.
. Return thermostat to normal setting.
Содержание EG-30 THRU -75
Страница 4: ...Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...
Страница 6: ...Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...
Страница 8: ...Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...
Страница 10: ...10 Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4...
Страница 15: ...15 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Lighting instructions Robertshaw 7200...
Страница 21: ...21 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Troubleshooting continued...
Страница 22: ...22 Part Number 550 110 032 0607 EG 30 thru 75 Series 4 and PEG 30 thru 65 Series 4 Troubleshooting continued...
Страница 23: ...23 Part Number 550 110 032 0607 Standing Pilot Boilers Control Supplement Troubleshooting continued...