WM97+ Control settings — Advanced
(continued)
&IGURE
$EFAULT$(70ERFORMANCE-ODE3ETTINGS
menus (see Figure 19, page 24 for access information)
Parameters
HIGH
NORMAL ECONOMY VACATION
DISABLED/
OFF
Description of Parameter
4ANK3TORAGE4ARGET
—
Upper Sensor Set Point
170°F
150°F
135°F
50°F
None
Target temperature to modulate boiler output to.
Boiler will modulate to either BOILER TARGET or
DHW Storage Target.
4ANK$IFF/N
2°F
2°F
2°F
0°F
Call for heat starts if upper tank temperature drops
below:
Tank Storage
minus
Diff On
4ANK3ENSOR$IFF
10°F
10°F
10°F
0°F
Call for heat starts if lower tank temperature drops
below:
Tank Storage
minus
Sensor Diff
minus
Diff On
"OILER4ARGET
—
When Upper Tank Temperature is
lower than:
Tank Storage
minus
Diff On
185°F
170°F
150°F
100°F
Maximum boiler outlet temperature the control
should use for the performance mode.
"OILER$IFF/N
2°F
2°F
2°F
10°F
Boiler restarts burner if there is a demand and boiler
temperature has dropped below:
Boiler Target
minus
Boiler Diff On
"OILER$IFF/FF
10°F
10°F
10°F
10°F
Control shuts down the burner if boiler supply water
temperature exceeds:
Boiler Target
plus
Boiler Diff Off
-INIMUM$(7
"LOWER3PEED
—
minimum RPM the
blower can target
during a DHW call
WM97+70
1100
1100
1100
1100
The adjustment limit for these are linked to the
boiler's absolute min as well as High Altitude.
See WM97+ Boiler manual for instructions to change
blower speed.
WM97+110
1400
1400
1400
1400
WM97+155
1300
1300
1300
1300
-AXIMUM$(7
"LOWER3PEED
—
maximum RPM the
blower can target
during a DHW call
WM97+70
4300
4300
4300
4300
The adjustment limit for these are linked to the
boiler’s absolute max as well as High Altitude.
See WM97+ Boiler manual for instructions to change
blower speed.
WM97+110
5650
5650
5650
5650
WM97+155
5500
5500
5500
5500