6)  Steam boiler secondary low water cut-off shall be a float type – manual 

reset. 

 

III. 

Burner(s) construction, features and requirements

 

1.  Burner fuel supply system and burner installation to conform to burner 

manufacturer’s installation instructions and applicable codes. 

2.  Burner motor characteristics:  

ˆ

 120/60/1, 

ˆ

 240/60/1, 

ˆ

 208/60/3, 

ˆ

 

240/60/3, 

ˆ

 480/60/3. 

3. Control 

characteristics 

120/60/1. 

4.  Burner fuel – natural gas 4.0” W.C. minimum, No. 2 fuel oil. 
5. Code(s) 

ˆ

 standard boiler, 

ˆ

 CSD-1, 

ˆ

 FM, 

ˆ

 IRI 

6.  Burner(s) to have UL label(s) supplied by the burner manufacturer. 
7.  Burner(s) designed to ensure high efficiency and good performance under 

forced draft conditions with 0.1” W.C. positive pressure at the flue collar. 

8.  Burner to be adjusted to provide 9.5 to 10.0% CO

2

 for gas and/or 11.5 to 12% 

CO

2

 with zero smoke for oil firing. 

9. Burner(s) 

manufactured 

by: 

ˆ

 Power-Flame, 

ˆ

 Gordon-Piatt. 

10.  Burner operating mode: 

ˆ

 on-off, 

ˆ

 low-high-off, 

ˆ

 low-high-low, 

ˆ

 

modulating 

 

A. 

Panel options – power on/fuel on light is standard on all burner(s) with panels. 

1)  Call For Heat 
2) Ignition On 
3) Pilot Failure 
4) Low Water 
5) Flame Failure 
6) Silencing Switch 
7)  Control Fuse and Holder 
8)  Post Purge Timer 
9) Alarm Bell 

 

B. 

Start-up and Service 

 

The contractor shall obtain the services of a factory authorized agent to provide 
burner light-off and adjustment. The start-up agent shall provide a burner light-
off report as written proof that the burner was adjusted to optimum 
performance. 

 

Authorized:  The agent shall provide a one year service warranty after start-up. 

 

Weil-McLain 

500 Blaine Street 

Michigan City, IN  46360-2388 

http://www.weil-mclain.com 

C-810(699) 

Содержание 94

Страница 1: ...output s at 100 firing rate MBH per boiler E Boiler s shall be manufactured by ISO 9001 registered company to conform to Section IV of the ASME Boiler and Pressure Vessel Code 1 Individual sections and section assembly to be hydrostatically pressure tested at factory in accordance with ASME requirements 2 Maximum allowable working pressure 50 PSIG water and 15 PSIG steam cast as part of section wi...

Страница 2: ... Boiler s Provided with cast in air elimination to separate air from circulating water Provided with expansion tank tapping to divert separated air to expansion tank Constructed to provide balanced water flow through entire section assembly using single supply and return connections for water No external headers are necessary for water Steam requires an external header 24 minimum from the waterlin...

Страница 3: ... temperature gauge with dial clearly marked and easy to read 4 ASME certified pressure relief valve set to relieve at 30 PSIG Optional relief valves available up to and including maximum allowable pressure Side outlet discharge type contractor to pipe outlet to floor drain or near floor avoiding any area where freezing could occur b Steam boiler s standard controls furnished 1 Low pressuretrol ope...

Страница 4: ...er to be adjusted to provide 9 5 to 10 0 CO2 for gas and or 11 5 to 12 CO2 with zero smoke for oil firing 9 Burner s manufactured by Power Flame Gordon Piatt 10 Burner operating mode on off low high off low high low modulating A Panel options power on fuel on light is standard on all burner s with panels 1 Call For Heat 2 Ignition On 3 Pilot Failure 4 Low Water 5 Flame Failure 6 Silencing Switch 7...

Отзывы: