2. Other 

manufacturer(s) 

or other Weil-McLain boiler(s) must comply with 

specifying engineer’s requirements, including: 

a)  Full intent of these specifications, and provide complete submittal 

including literature, wiring diagrams, fuel piping diagrams, and a list of 
similar installations.  

b)  Submittal to be presented to specifying engineer at least seven working 

days for approval before bid opening. Substitutions are not permitted after 
contract is awarded. 

c)  Burner(s) and Energy Management Control System(s) must be tested 

and approved for installation with specified boiler by boiler manufacturer. 

 

B. Boiler 

construction 

 

Boiler sections 

 

Assembled with short, individual draw rods. 

 

Cast with sealing grooves for high temperature sealing rope to assure 
permanent gas-tight seal. 

 

Sealed water-tight by elastomer sealing rings, not cast iron nipples. Each port 
opening is machined to completely capture sealing ring between sections. 

 

Must be hydro-wall design to provide completely water-cooled combustion 
chamber. 

 

Provided with sufficient tappings to install required controls. 

 

Limited 10 year warranty against workmanship and defects to be in writing by 
manufacturer. 

 

C. Boiler(s) 

 

Provided with cast-in air elimination to separate air from circulating water. 

 

Provided with expansion tank tapping to divert separated air to expansion tank. 

 

Constructed to provide balanced water flow through entire section assembly 
using single supply and return connections for water. No external headers are 
necessary for water. Steam requires an

 

external header 24” minimum from the 

waterline to the bottom of the header. 

 

Designed with a low silhouette to provide maximum headroom. 

 

Furnished with insulated burner mounting plate having necessary holes and 
tappings to mount burner. High temperature sealing rope is used to provide 
permanent gas-tight seal between front section and plate. 

 

Furnished with two observation ports (one in front and one in back) to allow 
visual inspection of the flame. 

 

Provided with cast iron flue collar with a built-in adjustable damper capable of 
being locked into place after adjustment. 

 

High temperature sealing rope used to provide permanent gas-tight seal 
between hood and section assembly. 

 

Furnished with cast iron cleanout plates to cover cleanout openings on the 
front of the boiler(s). 

 

Elastomer sealing rings are to be used to provide permanent water-tight seal 
between sections. Unlike cast iron or steel push nipples, the elasticity of the 
seals fills any gaps caused by misalignment or expansion or contraction. 

Содержание 94

Страница 1: ...output s at 100 firing rate MBH per boiler E Boiler s shall be manufactured by ISO 9001 registered company to conform to Section IV of the ASME Boiler and Pressure Vessel Code 1 Individual sections and section assembly to be hydrostatically pressure tested at factory in accordance with ASME requirements 2 Maximum allowable working pressure 50 PSIG water and 15 PSIG steam cast as part of section wi...

Страница 2: ... Boiler s Provided with cast in air elimination to separate air from circulating water Provided with expansion tank tapping to divert separated air to expansion tank Constructed to provide balanced water flow through entire section assembly using single supply and return connections for water No external headers are necessary for water Steam requires an external header 24 minimum from the waterlin...

Страница 3: ... temperature gauge with dial clearly marked and easy to read 4 ASME certified pressure relief valve set to relieve at 30 PSIG Optional relief valves available up to and including maximum allowable pressure Side outlet discharge type contractor to pipe outlet to floor drain or near floor avoiding any area where freezing could occur b Steam boiler s standard controls furnished 1 Low pressuretrol ope...

Страница 4: ...er to be adjusted to provide 9 5 to 10 0 CO2 for gas and or 11 5 to 12 CO2 with zero smoke for oil firing 9 Burner s manufactured by Power Flame Gordon Piatt 10 Burner operating mode on off low high off low high low modulating A Panel options power on fuel on light is standard on all burner s with panels 1 Call For Heat 2 Ignition On 3 Pilot Failure 4 Low Water 5 Flame Failure 6 Silencing Switch 7...

Отзывы: