Shipped with insulated heavy gauge steel jacket(s) with durable powdered 
paint enamel finish. Jacket designed to be installed after connecting supply and 
return piping. 

 

D. 

Tankless heaters or indirect water heaters 

 

Provide (    ) internal tankless water heater(s) inserted into the right hand side 
of the tankless intermediate (TI) section in the opening provided. Allow 44” 
minimum clearance on right side of boiler for cleaning and servicing. Tankless 
openings must be on same side as the flue passage cleanout plates to 
minimize space requirements. 

 

E. Boiler 

foundation(s):

 

 

Installer to construct needed support and level concrete foundation(s) where 
boiler room floor is uneven or will not support the weight of the boiler(s). 

 

F. Boiler 

trim: 

1.  All electrical components to be of high quality and bear the UL label. 

a)  Water boiler(s) controls furnished: 

1)  Combination low temperature limit (operating) and high temperature limit 

control. 

2)  Low temperature limit set according to system design. High temperature 

limit set at least 20

°

F higher than the low limit (240

°

F is the maximum 

allowable water temperature). 

3) Combination 

pressure-temperature gauge with dial clearly marked and 

easy to read.  

4)  ASME certified pressure relief valve, set to relieve at 30 PSIG. Optional 

relief valves available up to and including maximum allowable pressure. 
Side outlet discharge type; contractor to pipe outlet to floor drain or near 
floor, avoiding any area where freezing could occur. 

 

b)  Steam boiler(s) standard controls furnished: 

1)  Low pressuretrol (operating) and high pressuretrol set at maximum 

pressure as a safety control. 

2)  Steam pressure gauge with dial clearly marked and easy to read. 
3)  Gauge cock water set with gauge glass, guards and aluminum water level 

plate. 

4)  ASME certified pressure relief valve, set to relieve at 15 PSIG. Side outlet 

discharge type; contractor to pipe outlet to floor drain or near floor, 
avoiding any area where freezing could occur. 

 

c)  Low water cut-off for water or steam boiler(s): 

1)  Boiler(s) to be furnished with UL labeled low water cut-off with ASME 

working pressure rating equal to the ASME rating of the relief valve. 

2)  Do not use quick-connect fittings on boiler(s). 
3)  Install cut-off according to manufacturer’s instructions. 
4)  Locate so burner shuts down if boiler water level falls below allowable 

safe waterline (steam boilers, ¼” above bottom of gauge glass). 

5)  Steam boiler primary low water cut-off shall be a float type – auto reset. 

Содержание 94

Страница 1: ...output s at 100 firing rate MBH per boiler E Boiler s shall be manufactured by ISO 9001 registered company to conform to Section IV of the ASME Boiler and Pressure Vessel Code 1 Individual sections and section assembly to be hydrostatically pressure tested at factory in accordance with ASME requirements 2 Maximum allowable working pressure 50 PSIG water and 15 PSIG steam cast as part of section wi...

Страница 2: ... Boiler s Provided with cast in air elimination to separate air from circulating water Provided with expansion tank tapping to divert separated air to expansion tank Constructed to provide balanced water flow through entire section assembly using single supply and return connections for water No external headers are necessary for water Steam requires an external header 24 minimum from the waterlin...

Страница 3: ... temperature gauge with dial clearly marked and easy to read 4 ASME certified pressure relief valve set to relieve at 30 PSIG Optional relief valves available up to and including maximum allowable pressure Side outlet discharge type contractor to pipe outlet to floor drain or near floor avoiding any area where freezing could occur b Steam boiler s standard controls furnished 1 Low pressuretrol ope...

Страница 4: ...er to be adjusted to provide 9 5 to 10 0 CO2 for gas and or 11 5 to 12 CO2 with zero smoke for oil firing 9 Burner s manufactured by Power Flame Gordon Piatt 10 Burner operating mode on off low high off low high low modulating A Panel options power on fuel on light is standard on all burner s with panels 1 Call For Heat 2 Ignition On 3 Pilot Failure 4 Low Water 5 Flame Failure 6 Silencing Switch 7...