62
3.6 DIP switch configuration
Use the DIP switches to configure the Modbus device address (SW 1) and the RS–485
serial settings (SW 2). The photo shows the factory default settings.
SW1 – The following table specifies the binary coding of the Modbus device address
via DIP switches. The factory default slave address is 1 (i.e. SW 1.1 in the ‘on’ position
and SW 1.2 to SW 1.8 in the ‘off’ position). As an example the DIP switch coding for
Modbus address 175 is shown (10101111 in binary).
SW 1.1 SW 1.2 SW 1.3 SW 1.4 SW 1.5 SW 1.6 SW 1.7 SW 1.8
Weight
2
0
(LSB)
2
1
2
2
2
3
2
4
2
5
2
6
2
7
(MSB)
Address
increment
1
2
4
8
16
32
64
128
Example address 175
ON
ON
ON
ON
OFF
ON
OFF
ON
Содержание Transclinic 14i+
Страница 2: ......
Страница 74: ...74 2 2 1...
Страница 75: ...75 2 2 ISO 7000 0434B X1 X4 X2...
Страница 76: ...76 X1 X4 X1 X4 X2 15 2 3 Transclinic DC 2 PV Modbus RTU SCADA PLC RS485 0 P DC 0 PV...
Страница 77: ...77 DC IEC61724 SPD Transclinic Modbus SPD ON OFF OFF Transclinic DC SCADA DC Transclinic PV DC Transclinic...
Страница 79: ...79 3 DIP 5 40 80 31 50 40 PV 1 kV...
Страница 82: ...82 3 2 PV PV X1 X4 X2 2 X1 X4 PV PV X2 PV PV PV PCS DC PV IEC 60947 DC 21B PCS...
Страница 83: ...83 PV Transclinic X1 X4 X2...
Страница 86: ...86 PV PV X2 PV X2 2 1 PV X1 X4 3 3 X3 PV 0 0 Vdc 1 24 Vdc 2 X3 Transclinic 24 Vdc X3...
Страница 87: ...87 X3 0 2 2 5 mm2 0 2 4 mm2 7 mm 0 4 0 5 Nm 0 6 3 5 mm Transclinic X3 EMC 3m...
Страница 89: ...89 Transclinic 2 5 Adc DC DC X6 EMC 3m...
Страница 100: ...100 5 OFF Transclinic OFF OFF 15 5 40 31 80 40 50 PV 2 1 X1 X4 X2 DIN RS 485...
Страница 101: ...101...
Страница 103: ...103 LVD 2006 95 EC EMC 2004 108 EC CE WEEE 012 19 EU WEEE...
Страница 105: ...105...
Страница 110: ......