3.6 DIP switch configuration
Use the DIP switches to configure the Modbus device address (SW 1) and the RS–485
serial settings (SW 2).
The photo shows the factory default settings depending on the
model of Transclinic device
SW1 – The following table specifies the binary coding of the Modbus device address
via DIP switches. The factory default slave address is 1 (i.e. SW 1.1 in the ‘on’ position
and SW 1.2 to SW 1.8 in the ‘off’ position). As an example the DIP switch coding for
Modbus address 175 is shown (10101111 in binary).
SW 1.1 SW 1.2 SW 1.3 SW 1.4 SW 1.5 SW 1.6 SW 1.7 SW 1.8
Weight
2
0
(LSB)
2
1
2
2
2
3
2
4
2
5
2
6
2
7
(MSB)
Address
increment
1
2
4
8
16
32
64
128
Example address 175
ON
ON
ON
ON
OFF
ON
OFF
ON
To change ID number, baudrate or parity the process must be as it follows:
• configure the desired ID, baud rate or parity.
• Set the SW2.2 in ON position
• Switch-on the device
• Change the SW2.2 from ON to OFF
• Switch-off the device and wait 5 seconds (any LED might be ON)
• Switch-on again the device
Содержание 2008130000
Страница 2: ......
Страница 14: ...14 ...
Страница 19: ...19 Abisolieren Abisolieren Option 1 Option 2 empfohlen Crimpen Drücken Einführen Einführen ...
Страница 30: ...30 7UDQVFOLQLF 56 VODYH 7UDQVFOLQLF 56 VODYH 56 PDVWHU 7UDQVFOLQLF 56 VODYH GDLV FKDLQHG VKLHOG Abbildung 4 ...
Страница 37: ...37 ...
Страница 42: ......
Страница 54: ...54 ...
Страница 59: ...59 Strip Strip Option 1 Option 2 recommended Crimp Press Insert Insert ...
Страница 70: ...70 7UDQVFOLQLF 56 VODYH 7UDQVFOLQLF 56 VODYH 56 PDVWHU 7UDQVFOLQLF 56 VODYH GDLV FKDLQHG VKLHOG figure 4 ...
Страница 77: ...77 ...
Страница 82: ...82 ...
Страница 94: ...94 ...
Страница 99: ...99 被覆剥き 被覆剥き オプション 1 オプション 2 推奨 圧着 押し込み 挿入 挿入 ...
Страница 110: ...110 7UDQVFOLQLF 56 VODYH 7UDQVFOLQLF 56 VODYH 56 PDVWHU 7UDQVFOLQLF 56 VODYH GDLV FKDLQHG VKLHOG 56 歝 ඪ沐夝 図 4 ...
Страница 117: ...117 ...
Страница 126: ......
Страница 127: ......