5.1. POWER CONNECTIONS

DANGER!

Connect the motor properly to the power supply by means of safe and permanent contacts, always considering 
the data informed on the nameplate, such as rated voltage, wiring diagram, drive inputs, among others.

For power cables, switching and protection devices dimensioning, consider the rated motor current, the service factor, and 
the cable length, among others. For motors without terminal block, insulate the motor terminal cables by using insulating 
materials that are compatible with the insulation class informed on the nameplate. The minimum insulation distance between 
the non-insulated live parts themselves and between live parts and the grounding must meet the applicable standards and 
regulations for each country.

 

Make the power connections following nameplate indication. 

Three-phase:

 

Power input: L1, L2 and L3 terminals

 

Protective earth: PE - green screw

 

If used, connect the optional external harmonic filter (passive PFC) in series to the line conductor.

WEG declares that the WECM / Emerald eZA motor line is intended to be used as a part of an end-product and thus is 
not an independently used machine. All cables of this product need to be internally installed into the enclosure of the final 
product.

DANGER!

Always connect the equipment to the ground protection (PE).

ATTENTION!

The power supply that feeds the inverter shall have a solid grounded neutral.

5.2. CONTROL CONNECTIONS

 

Make the control connections following nameplate indication.

 Three-phase: 

 

DC voltage: VDC and GND terminals

 

DC current: ADC and GND terminals

 

Frequency duty-cycle / PWM: PWM and GND terminals

 

Speed feedback (reference): REF and GND terminals

 

10 VDC source: 10 V and GND terminals

 

24 VDC source: 24 V and GND terminals

 

RS485 communication: 485+, 485- and GND terminals

 

Alarm relay: NO, NC and COM terminals

5.3. EMC REQUIREMENTS FOR CONFORMING INSTALLATIONS

 

The standard Three-phase WECM / Emerald eZA mounting solution (drive attached to the motor) comply with EN IEC 

61800-3 / FCC requirements.

 

For optional decentralized mounting, the product class may change and the product may require the use of external 

filters. Consult WEG for the solution that better comply with your installation requirements.

 

WECM / Emerald eZA product may require the use of an external filter to comply with

 harmonic current emissions 

requirements (EN61000-3-2).

 Consult WEG about optional external filters. 

Power

Conducted

Radiated

2,2 kW – 4 kW

C3

C3

Table 4 - EMC Class - IEC100  

To meet the EMC levels in the Table 4, it is necessary to strictly comply with the installation configuration requirements 
below mentioned:

 

The maximum permissible cable lenght of the power supply must be within a maximum distance of 3 meters.

 

Grounding must be carried out on the drive cover in an isolated manner.

 

Measurements must be carried out under load, providing the air velocity over the motor as specified in the design.

NOTE!

The end user takes personal responsibility for the EMC compliance of the whole installation.

Содержание WECM

Страница 1: ...www weg net WECM Emerald eZA Manual 1 WECM Emerald eZA Three Phase Motors Installation Operation and Maintenance Manual Motors Automation Energy Transmission Distribution Coatings...

Страница 2: ...e we advise to make a careful and detailed study of the instructions contained herein before performing any procedures on the motor The noncompliance with the instructions informed in this manual and...

Страница 3: ...roduct as it may interfere with the proper operation of the device ATTENTION Any service on the internal parts of the motor must be performed by qualified personnel only since due to the attraction be...

Страница 4: ...erformed according to the applicable standards and that the shaft key has been securely fastened before the motor is started When available do not lift and or carry the product holding by the input ca...

Страница 5: ...verhung loads include belt tension and weight of sheave 3 Overhung load limits do not include any effect of unbalanced magnetic pull Only remove the corrosion protection grease from the shaft end and...

Страница 6: ...IP66 the drain plugs must remain at closed position being opened only during the motor maintenance procedures Slinger WECM Emerald product in vertical shaft up mounting should be fitted with water sl...

Страница 7: ...solid grounded neutral 5 2 CONTROL CONNECTIONS Make the control connections following nameplate indication Three phase DC voltage VDC and GND terminals DC current ADC and GND terminals Frequency duty...

Страница 8: ...o select between local or remote speed adjust Remove the lid from the back side of the drive cover Use the DIP switch identified as L R to select between local L or remote R Reinstall the lid to the b...

Страница 9: ...agea Lower than 2 VDC Zero motor is off From 2 to 10 VDC Maxb Minc 8 ISd 2 Min DC current Lower than 4 mA DC Zero motor is off From 4 to 20 mA DC Maxb Minc 16 ISd 4 Min Frequency Lower than 10 Zero mo...

Страница 10: ...value for the remote speed adjust signals can be changed Using the optional WEG EC Motor Speed Controller see item 6 5 Using the product local tact buttons only up to the maximum speed set by WEG EC M...

Страница 11: ...the back side of drive cover after the connections are done Maximum speed adjust Remove the lid from the back side of the drive cover Connect the external controller to the EC motor using the cable su...

Страница 12: ...regime considering the critical and special use of this function NOTE When the user activates the Fire Mode function he she acknowledges that the protection functions of the WECM Emerald eZA are disab...

Страница 13: ...g Figure 11 Modbus connecting After completing the above preparations please turn on the power of the ECM Motor Confirm the ECM Motor Modbus slaver address The default address is 0x55 85 2 Operation i...

Страница 14: ...and click write Figure 15 Step 3 After write in the new address the old one is disable Input the new address in Node and check communication Figure 16 Figure 15 Write address Figure 16 Check communic...

Страница 15: ...different serial configuration The serial parameters of inverter can be changed by Modbus command The register 0x0008 is used to set the baud rate writing the corresponding baud rate in the register 0...

Страница 16: ...00 08 00 03 06 96 00 00 02 00 01 D4 88 10 The slaver responses format R 13 33 31 114 55 10 00 08 00 03 0C 1E When slaver responses it means setting successfully 9 Modbus command and address 01 Request...

Страница 17: ...troller Read Register address 0x0002 R 03 FCT Max Speed Read Register address 0x0003 R 03 Current Max Speed Read Register address 0x0004 R 03 Read motor Target speed Read Register address 0x0005 R 03...

Страница 18: ...ss 0000 Table 9 Register table 11 Fault error code Error Code Fault Description 0x0001 DCBUS LOW 0x0002 DCBUS HIGH 0x0003 OVER CURRENT HARDWARE PROTECTION 0x0004 TEMPERATURE CRITICALLY HIGH 0x0005 LOC...

Страница 19: ...s Motor model Batch number and manufacturing date available in the motor nameplate refer to item 4 Installed software version available in the drive label refer to item 4 8 MAINTENANCE DANGER g Before...

Страница 20: ...hnical documents especially those set out in the product Installation Operation and Maintenance Manual as well as the applicable standards and regulations in force in each country Defects arising from...

Страница 21: ...position IM code EN 60034 8 2007 A1 2014 Rotating electrical machines Part 8 Terminal markings and direction of rotation EN 60034 9 2005 A1 2007 Rotating electrical machines Part 9 Noise limits EN 60...

Страница 22: ...en installed maintained and used in applications for which they were designed and in compliance with the relevant installation standards and manufacturer s instructions comply with the provisions of t...

Страница 23: ...ey were designed and in compliance with the relevant installation standards and manufacturer s instructions comply with the provisions of the following relevant United Kingdom statutory requirements w...

Страница 24: ...6 4000 motores weg net www weg net The values shown are subject to change without prior notice The information contained is reference values Cod 50119773 Rev 00 Date m a 05 2022 MOTORS For WEG s world...

Отзывы: