Installation and Connection
3
3-18 | UR11
The UR11 rectifier series was developed to be used in application with the CFW-11M (Modular Drive) inverter
series, which can be used in IT networks without modifications. In these cases consider the following:
The phase to ground or isolation fault indication must be processed by the user to indicate the failure
occurrence and/or block the inverter operation.
In order to use the UR11 for feeding other inverters, refer to the inverter respective manual.
3.4.6.4 Control Connections
Status LEDs
Relay outputs
+ 24 Vdc input
Figure 3.19 -
UR11 control cables connection points
The CIR11 (Rectifier Interface Board) is presented at
. It is necessary to provide a +
24 Vdc +/- 10 % external power supply to feed this board. This external power supply must have 300 mAdc
minimum capacity.
Table 3.8 -
XC1 connector signals of the CIR11
XC1
Standard Function
Specifications
1
+24 V
24 Vdc power supply.
24 Vdc @ 300 mA / ± 10 % external power supply.
2
-
No function.
3
0 V
0 V reference for the 24 Vdc external power supply.
High impedance grounded (4,7 MΩ).