
ENGLISH
Parameter
Description / Notes
It configures the operation mode of the Soft-Starter, in Trimpots and Dip Switch mode or HMI mode.
0 “(Trimpot and Dip Switch)” – the programming of the initial voltage, ramp time, motor
current setting and enabling of the protection devices is performed by means of the trimpots
and dip switch. The values programmed through the serial communication is not used.
1 “HMI” - the programming is performed through the serial communication. The values
programmed through trimpots and dip switch is not used.
Note:
In HMI mode (P220=1) the trimpots and dip switch programming is ignored. The start voltage,
ramp times, motor current setting and the protection enabling is programmed through the
parameters P101, P102, P104, P105 and P106.
It configures the DI 1 digital input to operate according to the codes described below.
0- “Not used”, DI 1 digital input is disabled. The enabling commands are only accept via
serial communication (V03).
1- “Enable/Disable”, enabling only via digital input. The enabling commands via serial
communication are ignored.
2- “External Fault”, it acts only if the DI 1 digital input is open. It can also be used as additional
load protection. Example: thermal protection of the motor through dry contact (without voltage)
of a protection relay (Thermostat).
The enabling commands are only accepted via serial communication (V03).
It enables the relay (14/23 – 24) to operate according to the following parameter setting:
1- Function “Full voltage” – the relay closes the contact only after the Soft-Starter reached
100% of Un (By-pass), and opens the contact when the Soft-Starter has received a switch-
Off order.
2- Function “Error”, the relay closes the N.O. contact when the SSW-05 is with no error.
3- Function “Logic Command”, the relay opens and closes the relay contact according to the
BIT 5 status of the V03 basic variable.
Configures the SSW-05 models.
Its function is to set the software so the current indication in Ampere (P003) is correct.
The possible configurations of the SSW-05 model are:
0 = 3A
1 = 10A
2 = 16A
3 = 23A
4 = 30A
5 = 45A
6 = 60A
7 = 85A
It defines the address at which the Soft-Starter will respond on the communication network
between all equipment connected to this network.
This parameter has the purpose to set the action to be taken when an error indication occurs.
Note:
To attribute a function to this parameter, set P314 different from 0 = Off.
Values for P313:
1- It indicates only error.
2- Indicates error and disables the Soft-Starter by ramp. If the programmed deceleration time
is equal to 0 sec, the motor driven by the Soft-Starter will be stopped by inertia.
3- Indicates error and causes general disabling of the Soft-Starter. It can be used as emergency
stopping.
4- Indicates error and program P264 with the value 1. The bit 0 of V03 is reseted.
P220
HMI/(Trimpots and Dip
Switch) Selection
P264
Programmable
Digital Input DI 1
P277
Programmable
Relay Output (14/23 – 24)
P295
Rated Current of the
Soft-Starter
P308
Network Address
P313
Action of the Serial
Communication
Verification
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]