Overcurrent
Phase loss
Incorrect phase sequence
Locked rotor
Motor overload
Automatic reset
-
-
-
-
-
-
-
-
-
-
Example:
P106 = 13 Hex
1 - Enabled - Overcurrent
1 - Enabled - Phase loss
0 - Disabled - Incorrect phase sequence
0 - Disabled - Locked rotor
1 - Enabled - Motor overload
0 - Disabled - Automatic reset
13Hex = 010011bin
Parameter
Description / Notes
The Table below shows the combination of the enabled diagnostics and the corresponding
value to be programmed at P106.
Diagnostic Configuration
Value Programmed
at P106 (hexadecimal)
Automatic Reset
Motor Overload
S
tall
Incorrect
Phase sequence
Phase Loss
Overcurrent
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
10
11
12
13
14
15