71
6
DETAILED PARAMETER DESCRIPTION
6.3.21 P47 - Auto-Reset
Time (s)
When an error occurs, except E01, E02 and E07 or E2x,
the Soft-Starter can realize an automatic reset after the
programmed time at P47 has been elapsed.
If P47=OFF, the Auto-Reset will not occur.
After the Auto-Reset time has been elapsed and the
same error occurs three consecutive times (*), the Auto-
Reset Function will be disabled. Thus, if an error occurs
four consecutive times, this error remains on the display
(and the Soft-Starter will be disable).
(*) an error will be considered consecutive, if it occurs within 60
seconds after has been executed the last Auto-Reset.
P45 -
Pump Control
OFF, ON
Possible Values
Factory
Standard
OFF
Factory
Standard
min.
Range
max.
P47 -
Auto-Reset Time
shortest step
OFF, 10s
1s
600s
OFF
6.4 - CONFIGURATION PARAMETERS - P28, P43, P44, P46, P50...P57, P61...P64
SSW-03 Plus permits two modes of operation: standard con-
nection or connection within the motor delta connection.
P28=OFF - Standard connection uses the Soft-Starter in the
normal star or delta line connection.
P28=ON - Motor inside delta connection uses the Soft-Starter
connected by the six motor leads in the motor phases.
6.4.1 - P28 - Operation
Mode
NOTE!
If no manometer is installed in the pipelines, the hydraulics
ram can be observed through the pressure relief valves.
NOTE!
Excessive acceleration or deceleration times can cause motor
overheating. Program them for your application as short as
possible.