9.1 CONFORMITY
The SSW-03 line, the models 120...580A with 200V to 400
rated voltage were tested too meet the following.
EMC Directive 89/336/EEC (Electromagnetic Compatibility),
using a Technical Construction File and the following
standards:
EN60947-4-2: Low-voltage switchgear and controlgear Part
4, contactors and motor-starters Section 2. AC
semiconductor motor controllers and starters.
Low Voltage Directive (LVD) 73/23/EEC
ATTENTION!
The SSW-03 line has been designed for class A equipment.
Use of the products in domestic environments may cause radio
interference, in which case the user may be required to
employ additional mitigation methods.
NOTE!
The conformity of the Soft-Starter to any standard does not
guarantee that the entire installation will conform.
Many other factors can influence the total installation. Only
direct measurements can verify total conformity.
9.1.1 EMC AND LVD
DIRECTIVES
9.1.2 REQUIREMENTS
FOR
CONFORMING
INSTALLATIONS
9.1.2.1 EMC
DIRECTIVE
The following items are required for CE conformance:
1.
The Soft-Starters must be installed into closed metallic
boxes or panels that have a door only able to be opened
with a tool. A suitable cooling must be provided to
ensure that the temperature will be within the allowed
range. See item 3.1.1.
2.
Output cables (motor cables) must be armored, flexible
armored or installed inside a metallic conduit or
trunking with equivalent attenuation.
3.
Control (I/O) and signal wiring must be shielded or
installed inside a metallic conduit or trunking with
equivalent attenuation.
4.
The remote keypad (External HMI-3P) cable must be
shielded or installed inside a metallic conduit or
trunking with equivalent attenuation.
5.