Parameterization
SRW 01 | 5-23
5
5.4.7.2 Operation Diagram – Dahlander Starter
Low Speed
High
Speed
Stop
O1 - K1
O2 - K2
O3 - K3
Reset
Trip
Check Back
Imotor
Motor Transition
Time
Check Back
Aux. I14
P212
Figure 5.15:
Operation diagram for the Dahlander Starter operation mode
5.4.8 Pole Changing Starter
In this mode a Pole Changing Starter for three-phase motors with two windings is configured. The digital output
O1 is reserved (internal use) for running the motor at the low speed. The digital output O2 is reserved (internal use)
for running the motor at the high speed. The digital outputs O3 and O4 can be used according to the customer’s
needs (free).
In case of a Trip, the digital outputs O1 and O2 switch off the starting contactors, thus stopping the motor. For the
Control Unit (UC) connection diagram presented in the
Item 5.4.8.1 Connection Diagram - Pole Changing Starter on
, the digital inputs and outputs are configured according to the
Table 5.11:
Configuration of the digital inputs and outputs for the Two Winding Starting operation mode
Digital Inputs/Outputs
Function
Local/Remote Commands Using Digital Inputs
Control Logic
3 wires (P230 = 1)
(Pushbuttons)
Control Logic
2 wires (P230 = 0)
(Switch)
I11
Stop pushbutton
Free
I12
Start high speed
pushbutton
Start high speed/ stop
switch
I13
Start low speed
pushbutton
Start low speed/stop
switch
I14
(*)
Check Back
I15
Free
I16
Free
O1
K2 - low speed contactor operation
O2
K1 - high speed contactor operation
O3
Ladder
O4
Ladder
(*)
Adjust P208 according to the application.