SRW 01 | 6-11
6
P052 – Earth Fault Level
Adjustable
Range:
0 to 200 %
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the earth fault current as a percentage of the adjusted current (P401 or P402).
P053 – Voltage Unbalance Level
Adjustable
Range:
0 to 100 %
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the percentage of voltage unbalance in relation to the average voltage (P004) and the voltages L1-L2
(P033), L2-L3 (P034) and L3-L1 (P035).
P060 – Number of Starts
Adjustable
Range:
0 to 65535
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the number of motor starts.
P061 – Number of Overload Trips
Adjustable
Range:
0 to 65535
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the number of overload trips.
P062 – Number of Current Imbalance Trips
Adjustable
Range:
0 to 65535
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the number of current imbalance trips.
P063 – Number of Earth Fault Trips
Adjustable
Range:
0 to 65535
Factory
Setting:
-
Proprieties:
RO
Description:
It informs the number of earth fault trips.