Functional Description
.
42 | ECW500
𝐼
𝐸𝑋𝐶
= 𝐼
𝐸𝑋𝐶_𝐸𝑂𝑆
×
𝑉
10𝑉_𝑚𝑒𝑑𝑖𝑑𝑎
10
𝐼
𝐸𝑋𝐶
= 𝐼
𝐸𝑋𝐶_𝐸𝑂𝑆
×
(𝐼
4−20𝑚𝐴_𝑚𝑒𝑑𝑖𝑑𝑎
− 4)
16
In which:
𝑉
10𝑉_𝑚𝑒𝑎𝑠𝑢𝑟𝑒
is the measured voltage at the analog input (40028)
𝐼
4−20𝑚𝐴_𝑚𝑒𝑎𝑠𝑢𝑟𝑒
is the current measured at the analog input (40026).
𝐼
𝐸𝑋𝐶_𝐸𝑂𝑆
is the full scale adjusted (30256).
NOTE!
With the paramater 31028 enabled the ECW500 will not generate any DC voltage at the output
(terminals 49 and 50, F+ / F-) while in operation (status On .
6.5.4
MTVC_DROOP
(Mode: Terminal Voltage Control with DROOP) In this mode, the ECW500 operates in the load compensation
mode, based on reactive power that the synchronous machine is generating or absorbing. To do this, an
impedance is simulated at the machine terminals and the voltage is regulated in point inside or outside of the
synchronous machine. In this mode, the operation is always in parallel with the network (online) or in parallel with
a generator set.
Two compensation modes are available: droop and line-drop compensation.
In the droop mode, the reference voltage is reduced considering the increase of the reactive power at the
output of the synchronous machine.
On the other hand, in the line-drop compensation mode, the ECW500 regulates the voltage in a point outside
the machine, in the step-up transformer or even in a point along the transmission system. The compensation
produces an increasing reference voltage for the increase of the reactive power at the output of the machine.
For operation on MTVC DROOP mode, the user must adjust the compensation constant of this mode
(parameter 30216), which is a percentage value of the nominal power of the machine.
When the compensation constant is positive, the droop compensation is performed.
When it is negative, the line drop compensation is active.
The equation below shows the value of voltage Droop that will be subtracted from (or added) of (to the) main
reference.
𝑉
𝐷𝑅𝑂𝑂𝑃
= %
𝐷𝑅𝑂𝑂𝑃
×
𝑉
𝑟𝑎𝑡𝑒𝑑
√3 × 𝐼
𝑟𝑎𝑡𝑒𝑑
×
𝑄
𝑚𝑒𝑎𝑠𝑢𝑟𝑒𝑑
𝑉
𝑚𝑒𝑎𝑠𝑢𝑟𝑒𝑑
In which:
DROOP
%
is the compensation constant of the droop/line-drop modes (30216);
rated
V
is the rated voltage of the synchronous machines (30058);
rated
I
is the rated current of the synchronous machine (30060);
measured
Q
is the measured single-phase reactive power (40016);
measured
V
is the average effective voltage measured of the three phases (40006).