![WEG ECW500 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/weg/ecw500/ecw500_user-manual_950598012.webp)
Quick Parameter Reference
.
4 | ECW500
Modbus
Address
Description
Adjustable Range
Factory
Setting
Setting
Proper
.
30210
Parallel mode selection
0 = Off
1
1 = Droop
31028
External Power Module
0 = OFF, 1 = ON
0
31032
Transition time between modes
0 to 10000 s
10 s
SETPOINTS
30212
MTVC Setpoint
0.0 x V
nom
to 1.5 x V
nom
380 V
30214
MECC Setpoint
0.00 x Iexc
nom
a 1.50 x Iexc
nom
1.00 A
30216
DROOP Setpoint
-30.0 to 30.0 %
5.0 %
30218
MRPC Setpoint
-1.2 x P
nom
to 1.2 x P
nom
0 Var
30220
MPFC Setpoint
-0.01 a 0.01
1.00
30222
Minimum MTVC Setpoint
0.00 x V
nom
to 1.00 x V
nom
0.70 x V
nom
30224
Maximum MTVC Setpoint
1.00 x V
nom
to 1.50 x V
nom
1.20 x V
nom
30226
Minimum MECC Setpoint
0.00 x Iexc
nom
to 1.00 x Iexc
nom
0.00 x Iexc
nom
30228
Maximum MECC Setpoint
0.00 x Iexc
nom
to 1.20 x Iexc
nom
1.20 x Iexc
nom
30230
Minimum MRPC Setpoint
-1.20 x P
nom
to 1.20 x P
nom
-1.00 x P
nom
30232
Maximum MRPC Setpoint
-1.20 x P
nom
to 1.20 x P
nom
1.00 x P
nom
30234
Maximum MPFC Lag
1.00 a 0.01
0.50
30236
Minimum MPFC Lead
-1.00 a -0.01
-0.50
30238
Setpoint MTVC Preposition
0.00 x V
nom
a 1.50 x V
nom
380 V
30240
Setpoint MECC Preposition
0 a 1.5 x Iexc
nom
0.50 A
30242
Setpoint MRPC Preposition
-1.2 x P
nom
a 1.2 x P
nom
0 Var
30244
Setpoint MPFC Preposition
-0.01 a 0.01
1.00
30246
Enable MECC reference tracking
0 = False, 1 = True
0
31016
Enable DI for Inc/Dec of reference
0 = Disabled, 1 = Enabled
1
31036
Enable MTVC reference tracking
0 = False, 1 = True
0
31038
Enable MRPC reference tracking
0 = False, 1 = True
0
31040
Enable MPFC reference tracking
0 = False, 1 = True
0
31042
Enable Follower on MTVC
0 = False, 1 = True
0
31044
Enable MRPC Follower
0 = False, 1 = True
0
31046
Enable MRPC Follower
0 = False, 1 = True
0
31048
Source for Setpoint
0 = Parameter
0
1 = Analog Input
2 = Par Analog Input
REGULATORS
30016
Proportional gain MTVC
0.0 to 99.999
0.150
30018
Integral gain MTVC
0.0 to 99.999
0.250
30020
MTVC Derivative gain Kd
0.0 to 9.999
0.020
30022
MECC Proportional gain
0.0 to 99.999
0.250
30024
MECC Integral gain
0.0 to 99.999
0.500
30028
Proportional gain MRPC
0.0 to 99.999
0.100
30030
Integral gain MRPC
0.0 to 99.999
0.200
30034
Proportional gain MPFC
0.0 to 99.999
0.010
30036
Integral gain MPFC
0.0 to 99.999
0.020
LIMITERS
Excitation Overcurrent (LEOC)
30132
LEOC High level
0 to 2000.0 A
1.0 A
30134
LEOC Time
0 to 60 s
10 s
30140
LEOC Low level
0.1 a 2000.0 A
0.5 A
30142
LEOC enable
0 = False, 1 = True
0
30040
LEOC Proportional gain Kp
0.0 to 99.999
0.250
30042
LEOC Integral gain Ki
0.0 to 99.999
0.500
Terminal Overcurrent (LTOC)
30124
LTOC Enable
0 = False, 1 = True
0
Содержание ECW500