Functional Description
.
ECW500 | 37
Figure 6.11
Transition necessary at the digital inputs on the Mantained Button Mode
6.2.1
ON Digital Input
The ON digital input is used to enable the excitation of the ECW500, making it run in the pre-configured
operating mode.
6.2.2
OFF Digital Input
The OFF digital input is complementary to the ON input and it is used to disable the excitation of the ECW500.
The OFF command has priority over the ON command.
6.2.3
MTVC Digital Input
The MTVC digital input is used to change the operating mode of the ECW500 to MTVC (Mode: Terminal Voltage
Control).
6.2.4
MECC Digital Input
The MECC digital input is complementary to the MTVC input and it is used to change the operating mode of the
ECW500 to MECC (Mode: Excitation current Control). The MECC command has priority over the MTVC
command.
6.2.5
ENABLE PARALLEL Digital Input
The ENABLE PARALLEL digital input is used to change the operating mode of the ECW500 to MTVC DROOP
(Mode: Terminal Voltage Control with DROOP). It can be used in a complementary way to the DISABLE
PARALLEL digital input in Maintained Button mode. It only runs if the ECW500 is enabled. If the ECW500 is
disabled and this input is activated, a fault warning is generated.
6.2.6
DISABLE PARALLEL Digital Input
The DISABLE PARALLEL digital input is complementary to the ENABLE PARALLEL input and it is used to
disable the online mode or parallel mode and puts the ECW500 into the MTVC or MECC mode, according to
the previous configuration of the offline operating mode. It can be used as in a complementary way to the
ENABLE PARALLEL digital input in the Maintained Button mode.
If the ECW500 is running in the online MPFC or MRPC modes and the DISABLE PARALLEL digital input is
activated, the ECW500 will directly go to the offline MTVC or MECC mode according to the previous
configuration. If the digital inputs of the parallel and online mode are configured to run in the "button
maintained", the disable command must be executed in both the disable online input and disable parallel digital
inputs.