![WEG Drive Scan Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/weg/drive-scan/drive-scan_manual_950705039.webp)
5
CONNECTING A DEVICE TO THE DRIVE SCAN
5.6 SOFT-STARTER SSW900
5.6.1 RS-485
To connect the SSW900 to the WCD-ED300 via the RS-485 communication interface using the Modbus-RTU
protocol, it is necessary to install on the Soft-Starter the accessory CRS485-W listed in
Table 5.16
, which can be
used with firmware version 1.0 and above of the SSW900.
Refer to the SSW900 Modbus-RTU Communication guide, which can be obtained from the download center at
, for additional information.
Table 5.16:
RS-485 hardware accessory of the SSW900 compatible with the Modbus RTU protocol
Accessory
WEG item
Parameters
Pin
Signal
CRS485-W
12966043
Table 5.17
1
B (+)
2
A (-)
3
GND
4
Shield
Table 5.17:
Parameters related to the RS-485 communication accessories
Parameter
Net ID
Description
Values range
C8.2.1
730
Serial protocol
2 = Modbus RTU
C8.2.2
731
Serial address
1 a 247
C8.2.3
732
Serial baud rate
0 = 9600 bps
1 = 19200 bps
2 = 38400 bps
3 = 57600 bps
C8.2.4
733
Serial interface byte configuration
0 = 8 bits, no parity, 1 stop bit
1 = 8 bits, even parity, 1 stop bit
2 = 8 bits, odd parity, 1 stop bit
3 = 8 bits, no parity, 2 stop bits
4 = 8 bits, even parity, 2 stop bits
5 = 8 bits, odd parity, 2 stop bits
C8.2.5.1
740
Timeout mode
0 = Inactive
1 = F128 fault
2 = A128 alarm
C8.2.5.2
741
Timeout error action
0 = Only indicates
1 = Ramp stop
2 = General disable
3 = Go to LOC
4 = Go to REM
C8.2.5.3
734
Timeout
0,0 a 999,0s
5.6.2 ETHERNET
To connect to the WCD-ED300 via Ethernet GbE1 communication interface using the Modbus TCP protocol, it is
necessary to install on the SSW900 the accessory CMB-TCP-N listed in
Table 5.18
.
Low Voltage Devices | 5-20
Содержание Drive Scan
Страница 2: ......
Страница 4: ...Summary of reviews Version Revision Description 1 0X 00 First edition...
Страница 11: ...2 INSTALLATION RECOMMENDATIONS Low Voltage Devices 2 2...
Страница 58: ...6 SETTING THE DRIVE SCAN ON THE MFM Figure 6 22 RS 485 network con guration Low Voltage Devices 6 13...
Страница 59: ...6 SETTING THE DRIVE SCAN ON THE MFM Low Voltage Devices 6 14...
Страница 71: ...8 SETTING THE IP ON WINDOWS 10 Click on OK Figure A 7 Figure A 7 Changing IP Low Voltage Devices 8 3...
Страница 72: ......
Страница 73: ......