DRIVE SCAN COMMUNICATION
4.3 RS-485 CONNECTOR
Table 4.2:
Signals of the WCD-ED300 Drive Scan RS-485 Connector
Pino
Sinal
1
Negative RS-485
2
GND
3
Positive RS-485
4
Positive RS-485
5
GND
6
Negative RS-485
4.4 NETWORK SETTINGS
All the devices connected to physical networks, whether via RS-485 or Ethernet, must have the same baud rate,
data bit, parity and stop bit settings, so that the respective network works correctly.
4.5 NUMBER OF MONITORED ASSETS
The Drive Scan WCD-ED300 allows connecting and monitoring up to 10 assets on the RS-485 network and up
to 10 assets on the Ethernet network, for a maximum of 20 assets.
Chapter 5
describes the settings and possible
ways of connecting the low voltage frequency inverters to the Drive Sca.
In the case of the SRW01, the WCD-ED300 Drive Scan allows connecting and monitoring up to 20 relays on the
Ethernet network . Note: It is only possible to monitor the SRW01 on Ethernet models.
Chapter 5.7
describes the
settings and possible ways of connecting the relay to the Drive Scan.
4.6 INTERNET CONNECTION REQUIREMENTS
For the proper operation of the Drive Scan and connection to the MFM cloud, the customer’s network must meet
some requirements and have some releases.
Note
: to release the addresses, ports and internet access, ask the IT team in charge of the network.
The user’s network must not have VPN or PROXY;
The ports of
Table 4.3
and the IP addresses of
Table 4.4
must be accessible.
Table 4.3:
Addresses required for the Drive Scan communication with the MFM
Destino
IP
Objective
146.0.0.0/8
Send data to the MFM
3.225.66.59
Edge-Agent Maintenance
Dynamic address
Firmware update
Table 4.4:
Ports required for the Drive Scan communication with the MFM
Protocolo
Porta
Objetivo
TCP
80
Update/Support the Drive Scan
and Send data to the MFM
TCP
433
TCP
1883
TCP
8883
Low Voltage Devices | 4-2
Содержание Drive Scan
Страница 2: ......
Страница 4: ...Summary of reviews Version Revision Description 1 0X 00 First edition...
Страница 11: ...2 INSTALLATION RECOMMENDATIONS Low Voltage Devices 2 2...
Страница 58: ...6 SETTING THE DRIVE SCAN ON THE MFM Figure 6 22 RS 485 network con guration Low Voltage Devices 6 13...
Страница 59: ...6 SETTING THE DRIVE SCAN ON THE MFM Low Voltage Devices 6 14...
Страница 71: ...8 SETTING THE IP ON WINDOWS 10 Click on OK Figure A 7 Figure A 7 Changing IP Low Voltage Devices 8 3...
Страница 72: ......
Страница 73: ......