WEG Drive Scan Скачать руководство пользователя страница 19

4

DRIVE SCAN COMMUNICATION

4.3 RS-485 CONNECTOR

Table 4.2:

Signals of the WCD-ED300 Drive Scan RS-485 Connector

Pino

Sinal

1

Negative RS-485

2

GND

3

Positive RS-485

4

Positive RS-485

5

GND

6

Negative RS-485

4.4 NETWORK SETTINGS

All the devices connected to physical networks, whether via RS-485 or Ethernet, must have the same baud rate,
data bit, parity and stop bit settings, so that the respective network works correctly.

4.5 NUMBER OF MONITORED ASSETS

The Drive Scan WCD-ED300 allows connecting and monitoring up to 10 assets on the RS-485 network and up
to 10 assets on the Ethernet network, for a maximum of 20 assets.

Chapter 5

describes the settings and possible

ways of connecting the low voltage frequency inverters to the Drive Sca.

In the case of the SRW01, the WCD-ED300 Drive Scan allows connecting and monitoring up to 20 relays on the
Ethernet network . Note: It is only possible to monitor the SRW01 on Ethernet models.

Chapter 5.7

describes the

settings and possible ways of connecting the relay to the Drive Scan.

4.6 INTERNET CONNECTION REQUIREMENTS

For the proper operation of the Drive Scan and connection to the MFM cloud, the customer’s network must meet
some requirements and have some releases.

Note

: to release the addresses, ports and internet access, ask the IT team in charge of the network.

The user’s network must not have VPN or PROXY;

The ports of

Table 4.3

and the IP addresses of

Table 4.4

must be accessible.

Table 4.3:

Addresses required for the Drive Scan communication with the MFM

Destino

IP

Objective

broker.app.wnology.io

146.0.0.0/8

Send data to the MFM

hub.docker.com

3.225.66.59

Edge-Agent Maintenance

nexus3.weg.net

Dynamic address

Firmware update

Table 4.4:

Ports required for the Drive Scan communication with the MFM

Protocolo

Porta

Objetivo

TCP

80

Update/Support the Drive Scan
and Send data to the MFM

TCP

433

TCP

1883

TCP

8883

Low Voltage Devices | 4-2

Содержание Drive Scan

Страница 1: ...Motors Automation Energy Transmission Distribution Coatings Drive Scan Drive Specialist Low Voltage Devices Manual...

Страница 2: ......

Страница 3: ...Manual Series Low Voltage Devices Language English Document Number 10009054128 00 Build 00 Products Publication Date 10 2021...

Страница 4: ...Summary of reviews Version Revision Description 1 0X 00 First edition...

Страница 5: ...RED ASSETS 4 2 4 6 INTERNET CONNECTION REQUIREMENTS 4 2 5 CONNECTING A DEVICE TO THE DRIVE SCAN 5 1 5 1 RECOMMENDATIONS FOR CONNECTION VIA RS 485 5 1 5 2 CFW11 FREQUENCY INVERTER 5 2 5 2 1 RS 485 5 2...

Страница 6: ...7 2 POSSIBLE FORMS OF CONNECTIONS 5 25 5 7 3 MONITORING 5 25 6 SETTING THE DRIVE SCAN ON THE MFM 6 1 7 MONITORING DASHBOARD 7 1 7 1 ACCESS 7 1 7 2 FEATURES 7 1 7 3 PARAMETERS 7 1 8 DRIVE SPECIALIST 8...

Страница 7: ...re than one attribute such as last value average value minimum value and maximum value DHCP Dynamic Host Con guration Protocol Protocol that allows devices newly connected to a network to obtain an IP...

Страница 8: ...s designed to monitor information of different assets and assist in their maintenance The Drive Scan has dedicated rmware to integrate assets with the MFM platform performing several important tasks s...

Страница 9: ...e the Drive Scan please check that the package contains the items listed below Figure Figure 2 1 shows the accessories contained in the package 1x WCD Drive Scan 2x WiFi antenna 1x power supply 12V 2x...

Страница 10: ...the Drive Scan Physical Installation WARNING Be sure to power the Drive Scan within 110V to 220V power range with frequency from 50 to 60Hz Installation and con guration of the Drive Scan communicati...

Страница 11: ...2 INSTALLATION RECOMMENDATIONS Low Voltage Devices 2 2...

Страница 12: ...ter Estimation and prediction of variables through the Drive Specialist Access the WEG Motion Fleet management at https mfm wnology io ll out your registration and download the MFM guide To that end j...

Страница 13: ...access the website https mfm wnology io Enter your email and password and click on the SIGN IN button as shown in Figure 3 2 If you don t have an account create one through the Sign up link Figure 3 2...

Страница 14: ...ck on the Device option as shown in Figure 3 3 Figure 3 3 Registering a new device Step 3 Click on DEVICE button as shown in Figure 3 4 Figure 3 4 Adding a device Step 4 Select the Drive option and cl...

Страница 15: ...previously registered on the MFM as described in Chapter 6 Select Drive Scan and click on the CONTINUE button as shown in Figure 3 6 Figure 3 6 Ading a drive Step 6 Click on the ADD button as shown i...

Страница 16: ...owing settings are related to this choice Figure 3 8 Registering a drive Set the drive ModBus address Select the device model asset Enter the asset serial number Click on the SAVE button Step 8 Click...

Страница 17: ...3 WEG MOTION FLEET MANAGEMENT Step 9 A Figure 3 10 shows the dashboard of the drive newly registered on the MFM Figure 3 10 Dashboard of the drive registered on the MFM Low Voltage Devices 3 6...

Страница 18: ...x WCD ED300 DSLV x x x x x x x v1 00 v1 10 v1 17 v1 18 v1 19 v1 2x v1 6 0 v1 7 0 v1 8 x v1 9 x Wnology Edge Agent x x x x x x x x v1 0 xx v1 1 xx v1 2 xx v1 3 xx v1 4 xx v1 5 xx v1 6 0x v1 7 0xx v1 8...

Страница 19: ...e Ethernet network Note It is only possible to monitor the SRW01 on Ethernet models Chapter 5 7 describes the settings and possible ways of connecting the relay to the Drive Scan 4 6 INTERNET CONNECTI...

Страница 20: ...the termination resistors Figure 5 1 illustrates the situation SSW MVW CFW Drive Scan Termination Termination ModBus RTU network Figure 5 1 ModBus RTU network with WEG devices at the ends In case the...

Страница 21: ...rdware accessories of the CFW11 compatible with Modbus RTU protocol Accessory WEG Item Firmware CFW11 Parameters Pin Signal RS485 01 10051957 V3 14 Table 5 2 1 Negative RxD TxD 2 Positive RxD TxD CAN...

Страница 22: ...999 0 s Figure 5 4illustrates an RS 485 network among the CFW11 inverters using all communication modules Drive Scan RS485 1 2 3 CFW 11 4 RS485 01 A B GND CAN RS485 01 PLC11 A B RS485 05 A B GND Cabo...

Страница 23: ...PROFINETIO 05 11550548 Table 5 5 Parameters related to the MODBUSTCP 05 ETHERNETIP 05 and PROFINETIO 05 accessories Parameter Description Values range P0723 Anybus identi cation 0 Inactive 10 RS485 19...

Страница 24: ...5 192 27 255 255 255 224 28 255 255 255 240 29 255 255 255 248 30 255 255 255 252 31 255 255 255 254 P0849 Gateway 1 0 a 255 P0850 Gateway 2 0 a 255 P0851 Gateway 3 0 a 255 P0852 Gateway 4 0 a 255 Fig...

Страница 25: ...tomatically The parameters read are transformed into attributes which can be Only at initialization Last value read Average value Minimum value Maximum value Every 5 minutes the Drive Scan publishes t...

Страница 26: ...0037 Motor overload motorOverloadAvg motorOverloadMin motorOverloadMax Valor m dio Valor m nimo Valor m ximo P0002 Motor speed motorSpeedAvg Valor m dio P0009 Motor torque motorTorqueAvg motorTorqueMi...

Страница 27: ...GND signal pin CRS485 11710626 Table 5 9 6 7 8 Table 5 7 Parameters related to the RS 485 communication accessories Parameter Description Values range P0308 Serial address 1 a 247 P0310 Serial baud ra...

Страница 28: ...the Drive Scan a new reading cycle starts automatically The parameters read are transformed into attributes which can be Only at initialization Last value read Average value Minimum value Maximum val...

Страница 29: ...037 Motor overload motorOverloadAvg motorOverloadMin motorOverloadMax Valor m dio Valor m nimo Valor m ximo P0002 Motor speed motorSpeedAvg Valor m dio P0009 Motor torque motorTorqueAvg motorTorqueMin...

Страница 30: ...26 27 Table 5 9 Parameters related to the RS 485 communication accessories Parameter Description Values range P0308 Serial address 1 a 247 P0310 Serial baud rate 0 9600 bps 1 19200 bps 2 38400 bps P03...

Страница 31: ...192 0 0 11 255 224 0 0 12 255 240 0 0 13 255 248 0 0 14 255 252 0 0 15 255 254 0 0 16 255 255 0 0 17 255 255 128 0 18 255 255 192 0 19 255 255 224 0 20 255 255 240 0 21 255 255 248 0 22 255 255 252 0...

Страница 32: ...se readings as well as of the other assets connected to the Drive Scan a new reading cycle starts automatically The parameters read are transformed into attributes which can be Only at initialization...

Страница 33: ...037 Motor overload motorOverloadAvg motorOverloadMin motorOverloadMax Valor m dio Valor m nimo Valor m ximo P0002 Motor speed motorSpeedAvg Valor m dio P0009 Motor torque motorTorqueAvg motorTorqueMin...

Страница 34: ...s from pins 12 A 14 B and 16 GND The second interface consists of the signals from pins 20 A 22 B and 24 GND Table 5 12 RS 485 hardware accessories of the CFW500 compatible with Modbus RTU protocol Ac...

Страница 35: ...bE1 communication interface using the Modbus TCP protocol it is necessary to install on the CFW500 one of the accessories listed in Table 5 14 Table 5 14 Ethernet hardware accessories of the CFW500 co...

Страница 36: ...252 0 23 255 255 254 0 24 255 255 255 0 25 255 255 255 128 26 255 255 255 192 27 255 255 255 224 28 255 255 255 240 29 255 255 255 248 30 255 255 255 252 31 255 255 255 254 P0816 Gateway 1 0 a 255 P08...

Страница 37: ...nitialization Last value read Average value Minimum value Maximum value Every 5 minutes the Drive Scan publishes the attributes to the WEG Fleet Management platform In case of an internet connection f...

Страница 38: ...037 Motor overload motorOverloadAvg motorOverloadMin motorOverloadMax Valor m dio Valor m nimo Valor m ximo P0002 Motor speed motorSpeedAvg Valor m dio P0009 Motor torque motorTorqueAvg motorTorqueMin...

Страница 39: ...to the RS 485 communication accessories Parameter Net ID Description Values range C8 2 1 730 Serial protocol 2 Modbus RTU C8 2 2 731 Serial address 1 a 247 C8 2 3 732 Serial baud rate 0 9600 bps 1 19...

Страница 40: ...0 10 255 192 0 0 11 255 224 0 0 12 255 240 0 0 13 255 248 0 0 14 255 252 0 0 15 255 254 0 0 16 255 255 0 0 17 255 255 128 0 18 255 255 192 0 19 255 255 224 0 20 255 255 240 0 21 255 255 248 0 22 255 2...

Страница 41: ...ameters speci ed in Section 5 6 4 1 5 6 4 1 Attributes Cyclically Monitored by the SSW900 on page 5 23 After a cycle of all these readings as well as of the other assets connected to the Drive Scan a...

Страница 42: ...e motorVoltage Average value measurement S1 5 1 10 Active power outputPower Average value measurement S1 5 2 12 Apparent power apparentPower Average value measurement S1 5 3 14 Reactive power reactive...

Страница 43: ...rameter Description Values range P0751 Ethernet com munication status 0 Setup 1 Init 2 Wait Comm 3 Idle 4 Data Active 5 Error 6 Reserved 7 Exception 8 Access Error P0753 Ethernet baud rate 0 Auto 1 10...

Страница 44: ...nnected to the internet using the Ethernet port GbE0 if it does not have a proxy 5 7 3 MONITORING The Drive Scan continuously monitors the SRW01 parameters speci ed in Section 5 7 3 1 Attributes Cycli...

Страница 45: ...Last value measurement P052 Earth fault imbalance earthFault Last value measurement P053 Voltage imbalance level voltageUnbalance Last value measurement P060 Total starts number startsNumber Last val...

Страница 46: ...ive Scan Wi Fi antenna or by connecting a network cable to the GbE0 ethernet port For the Drive Scan con guration follow the instructions below Step 1 Connect an Ethernet cable between the computer an...

Страница 47: ...Drive Scan This manual has an appendix Chapter A with instructions regarding this procedure for Windows 10 Authenticate the WCD ED300 which by default is User weg Password weg Click on Login button Fi...

Страница 48: ...SCAN ON THE MFM Step 5 Check the Internet Status eld If the status read is Connected go to Step 8 or Disconnected go to Step 6 as shown in Figure 6 5 Figure 6 5 hecking the Drive Scan con guration Low...

Страница 49: ...e used Open network WPA2 PSK WPA2 Enterprise WEP EAP Type de nes the network authentication framework to be used None PEAP MSCHAPV2 PSK PEAP TTLS MSCHAPV2 Identity username to authenticate to the Wi F...

Страница 50: ...8 Information about the saving operation Figure 6 9 Drive Scan resetting Step 8 The Internet Status eld should display Connected Check if the elds Figure 6 10 MQTT Status displays Disconnected or Sele...

Страница 51: ...M Chapter 3 and click on Next according to Figure 6 11 Figure 6 11 MFM Email and password login elds Step 10 If successful go to Step 11 In case of failure Figure 6 12 wrong login or password click on...

Страница 52: ...ge Plants links the Drive Scan to a plant or Delete Device deletes the Drive Scan from the plant Clique no bot o Next Go to Step 12 if Manage Plants option Figure 6 13 Go to Step 14 if Delete Device o...

Страница 53: ...es the Drive Scan with another existing gateway on MFM Clique no bot o Next Go to Step 13 if Create Device option Figure 6 14 Go to Step 14 if Replace Device option Back return to Step 11 Figure 6 14...

Страница 54: ...rmation is required to unlink the Drive Scan from the MFM as shown in Figure 6 16 Click on the button Delete Go to Step 15 Back return to Step 11 Figure 6 16 Screen with information on unlinking the...

Страница 55: ...and click on Back return to Step 11 If the error persists return to the con guration tab use the Factory Reset option Figure 6 18 return to Step 1 it is necessary to redo all the settings Figure 6 17...

Страница 56: ...16 The new plant must have been con gured Figure 6 19 Click on the Save Con guration button Figure 6 7 Wait for the Drive Scan to restart Figure 6 9 Go to Step 17 Figure 6 19 Plant linked to the Drive...

Страница 57: ...twork mask related to the IP address of the Ethernet interface Gateway Gateway network IP address DNS 1 First DNS server IP DNS 2 Second DNS server IP Con gure the RS 485 serial network interface Figu...

Страница 58: ...6 SETTING THE DRIVE SCAN ON THE MFM Figure 6 22 RS 485 network con guration Low Voltage Devices 6 13...

Страница 59: ...6 SETTING THE DRIVE SCAN ON THE MFM Low Voltage Devices 6 14...

Страница 60: ...ill bring direct information about Identi cation of each asset Asset status Asset health Charts of the various monitored attributes Parameter history only available for the CFW11 The user can also cre...

Страница 61: ...f the chosen date with the current values Through the Request parameterization reading button it is possible to request the reading of the parameters inserting them as current values in the table Such...

Страница 62: ...nsumption page displays information on the inverter electrical energy consumption This energy is basically related to the mechanical power delivered by the motor driven by the inverter The user can vi...

Страница 63: ...ts of Figure 8 2 a Rated speed b b Half rated speed Figure 8 2 Example of the difference between mechanical power and electrical power at the inverter output W22 IR3 Premium Motor 500 CV 4 Poles measu...

Страница 64: ...ssessed through the reading of the inverter DC link voltage The average voltage of the DC link is directly related to the amplitude of the AC power supply effective value During braking moments that i...

Страница 65: ...desbalancemento de tens o 0 1 2 3 4 5 6 Cr tico Alerta F006 Desequil brio Falta de Fase na Rede Critical Error 120Hz harmonic for different voltage imbalance levels F006 Imbalance Phase Fault Output p...

Страница 66: ...fan exceeds this number of hours of operation it may present a failure especially a mechanical one A very common cause is the degree of air pollution in industrial applications exceeding the speci ca...

Страница 67: ...ult or a fan speed fault F174 Left Fan Speed Fault F175 Central Fan Speed Fault F176 Right Fan Speed Fault The indicated states are Figure 8 8 Normal 0 85 x rated speed fan speed Alert 0 70 x rated sp...

Страница 68: ...utton formerly Start Click on the Settings button Figure A 1 Figure A 1 Start button Step 2 Click on the Network and Internet option Figure A 2 Figure A 2 Netowrk and internet page Step 3 Click on the...

Страница 69: ...THE IP ON WINDOWS 10 Step 4 Double click on Ethernet Figure A 4 Figure A 4 Selecting the adapter Step 5 Click on the Properties button Figure A 5 Figure A 5 Changin ehternet properties Low Voltage De...

Страница 70: ...7 Write down the current settings of your network card because later it will be necessary to restore these settings Select the Use the following IP address option Set the IP address within the same ra...

Страница 71: ...8 SETTING THE IP ON WINDOWS 10 Click on OK Figure A 7 Figure A 7 Changing IP Low Voltage Devices 8 3...

Страница 72: ......

Страница 73: ......

Страница 74: ...WEG Drives Controls Automa o LTDA Jaragu do Sul SC Brazil Phone 55 47 3276 4000 Fax 55 47 3276 4020 S o Paulo SP Brazil Phone 55 11 5053 2300 Fax 55 11 5052 4212 automacao weg net www weg net...

Отзывы: