![Wecon LX3V-2TC-BD Скачать руководство пользователя страница 3](http://html1.mh-extra.com/html/wecon/lx3v-2tc-bd/lx3v-2tc-bd_mounting-instruction_949556003.webp)
LX3V-2TC-BD
2
WECON Technology Co., Ltd.
M8113
The flag of thermocouple switch in
CH2
OFF: K type
ON: J type
M8117
The flag of thermocouple switch in CH1
OFF: K type
ON: J type
D8112
CH1 temperature (unit: 0.1)
D8116
CH1 temperature (unit: 0.1)
D8113
CH2 temperature (unit: 0.1)
D8117
CH2 temperature (unit: 0.1)
3.
Dimension
Table 3-1
LED lights indicating
1)
LED1: ON when power ON.
2)
LED2: flashes when communications.
3)
LED3 (TC 1): On indicates enable, OFF indicates disable, flicker indicates exceeding the
measurement range.
4)
LED4 (TC 2): On indicates enable, OFF indicates disable, flicker indicates exceeding the
measurement range.
If the BD module is plugged into the old firmware version when on the host, all LEDs will be flashing.
4.
Specifications
1)
Please refer to the LX3V user manual for the general specification of LX3V-2TC-BD.
2)
LX3V-2TC-BD is powered supply by LX3V main unit.
Table 4-1
Item
Explanation
Analog circuitry
DC 24V ±10%, 70mA
Digital circuitry
DC 5V, 90mA (From the PLC internal power supply)
Applied sensor: 2-wire thermocouple(K/J)
L1+
Positive pole of CH1’s sensor
L1-
Negative pole of CH1’s sensor
FG
None
L2+
Positive pole of CH2’s sensor
L2-
Negative pole of CH2’s sensor