1.

 

Mounting instruction 

Before  the  installation  must  be  ensure  that  the  PLC  host  and  BD  associated  equipment  power  off. 

Please install the BD module in the corresponding position of the PLC, and lock the four standard screws. If 

environmental dust is bigger, please cover BD right part by PLC’s cover. Please do not power operation. 

 

Caution 

1)

 

This BD module only support the  following  firmware versions  or  later.  Users  can  check  the  PLC 
firmware version in D8001. 

 

LX3VP:25103; 

 

LX3V-A2:25015; 

 

LX3V-LX3VE:25201; 

 

A1:22007; 

 

LX2VA:24006; 

When  mounting  module  to  PLC,  all  the  lights  are  blinking  after  power  ON  PLC  please 
upgrade the firmware of PLC. 

2)

 

Please fixed BD module on the PLC, poor contact may lead to failure. 

3)

 

BD module and top cover of PLC’s tightening torque is 0.3 ~ 0.6 N.m. 

 

Warring 

Make  sure  to  power  off  the  PLC  before  mounting  or  removing  the  BD  module  and  put  the  cover  in 

right place. 

 

2.

 

Special feature 

1)

 

LX3V-2TC-BD module equips with 2 channels analog output. This module will be mounted in the 

PLC, so there is no need to change the installation area of the PLC. 

2)

 

The  type  to  AD  convert  of  LX3V-2TC-BD  is  a  thermocouple  input  type  (K/J),  and  the  converted 

digital  value  of  each  channel  is  stored  in  special  registers,  but  the  mode  of  analog-to-digital 

conversion cannot be changed. The corresponding channel as following table shows.   

Table 2-1 LX3V-2TC-BD address assignment 

Extension port 1 (far away from PLC LED)

 

Extension port 2 (near PLC LED)

 

Address

 

Description

 

Address

 

Description

 

M8112 

The  flag  of  thermocouple  switch  in 

CH1 
OFF: K type 
ON: J type 

M8116 

The flag of thermocouple switch in CH1 
OFF: K type 
ON: J type 

Содержание LX3V-2TC-BD

Страница 1: ...ON LX3V 2TC BD Module Website http www we con com cn en Technical Support liux we con com cn Skype fcwkkj or Jason chen842 Phone 86 591 87868869 QQ Group 465230233 Technical forum http wecon freeforums net ...

Страница 2: ...ead to failure 3 BD module and top cover of PLC s tightening torque is 0 3 0 6 N m Warring Make sure to power off the PLC before mounting or removing the BD module and put the cover in right place 2 Special feature 1 LX3V 2TC BD module equips with 2 channels analog output This module will be mounted in the PLC so there is no need to change the installation area of the PLC 2 The type to AD convert ...

Страница 3: ... the measurement range 4 LED4 TC 2 On indicates enable OFF indicates disable flicker indicates exceeding the measurement range If the BD module is plugged into the old firmware version when on the host all LEDs will be flashing 4 Specifications 1 Please refer to the LX3V user manual for the general specification of LX3V 2TC BD 2 LX3V 2TC BD is powered supply by LX3V main unit Table 4 1 Item Explan...

Страница 4: ...re cut off the electricity before installation disassembly to prevent electric shock or product damages Caution 1 Stay away from high voltage cables to avoid interference or surge 2 Grounding is required but please do not share the ground site with high voltage cable 3 Do not weld any cable ends and make ensure that the number of connecting cables no more than a predetermined number 4 Do not conne...

Страница 5: ...ple input mode and stored value in D0 and D2 6 2 Examples of Applications Since the LX3V 2TC BD does not have offset and gain functions if it needs for the values out of the standard specifications Additional programming orders will be needed to multiply or divide the converted value Caution Since the use of additional programming orders the converted precision and resolution of the analog Set CH1...

Страница 6: ...hermocouple input mode In Thermocouple input mode LX3V 2TC BD covert an analog value to a digital value in degrees Celsius If in the program is Fahrenheit as a unit it needs to be converted to Celsius value Fahrenheit and Celsius conversion formula Fahrenheit Celsius 9 5 32 the unit is 0 1 D10 D8112 9 D12 D10 5 D0 D12 320 D0 D8112 9 5 320 ...